107
Section V.
Parameter Function Table
more abundant and practical uses. For specifications please refer to A7 group.
Code
Description/
Keyboard Display
Setting Range
Factory
Setting
Change
Limit
PC.00
MS command 0
-100.0%~100.0%
0.0%
☆
PC.01
MS command 1
-100.0%~100.0%
0.0%
☆
PC.02
MS command 2
-100.0%~100.0%
0.0%
☆
PC.03
MS command 3
-100.0%~100.0%
0.0%
☆
PC.04
MS command 4
-100.0%~100.0%
0.0%
☆
PC.05
MS command 5
-100.0%~100.0%
0.0%
☆
PC.06
MS command 6
-100.0%~100.0%
0.0%
☆
PC.07
MS command 7
-100.0%~100.0%
0.0%
☆
PC.08
MS command 8
-100.0%~100.0%
0.0%
☆
PC.09
MS command 9
-100.0%~100.0%
0.0%
☆
PC.10
MS command 10
-100.0%~100.0%
0.0%
☆
PC.11
MS command11
-100.0%~100.0%
0.0%
☆
PC.12
MS command 12
-100.0%~100.0%
0.0%
☆
PC.13
MS command 13
-100.0%~100.0%
0.0%
☆
PC.14
MS command 14
-100.0%~100.0%
0.0%
☆
PC.15
MS command 15
-100.0%~100.0%
0.0%
☆
MS speed command can be used on three occasions
:
frequency source, VF saparation voltage
source, process PID set source.
Dimension of MS speed command is a relative value ranging from -100.0% to 100.0%. When used as
command source,
it’s the percentage of maximum frequency. When used as VF saparation voltage source,
it’s the percentage of motor rated voltage. When used as PID set source, dimension conversion is not
needed during the process.
MS command should be selected according to the different states of multi-function digit DI terminals.
For details please refer to P4 group.
PC.16
PLC running mode
Single running stop
0
0
☆
Single running end remaining final value
1
Continuous circulation
2
Simple PLC command can be used on two occasions
:
frequency source, VF saparation voltage source.
Fig 5-30 is the schematic diagram of simple PLC that used as frequency source. Positive & negative of
PC.00~PC.15 determines the running direction.
PLC has 3 running modes as frequency source(VF saparation voltage source is not provided with the
3 modes)
:
0
:
Single running stop
Upon completion of one single cycle of the inverter, it will stop automatically and will not start until
running command is given again.
1
:
Single running end remaining final value
Upon completion of one single cycle of the inverter, the inverter will remain the running frequency and
direction of last one phase. After the inverter restarted upon stop, it will run from the initial status of PLC.