Section V.
Parameter Function Table
P0.05 and P0.06.
3. When the frequency source is pulse input reference, it is similar to the analog value.
Prompt
:
There is difference between the auxiliary frequency source Y selection and the main
frequency source X setup value. That is to say, P0.03 and P0.04 cannot use the same frequency reference
channel.
P0.05
Auxiliary frequency source
Y range selection
Relative to maximum frequency
0
0
☆
Relative to frequency source X
1
P0.06
Auxiliary frequency source
Y range
0%~150%
0
☆
When the frequency source selection is frequency overlap reference(P0.07 is set to 1
、
3 or 4), it is
used to determine the adjustment range of auxiliary frequency source. P0.05 is used to determine the
relative object within the range. If it is relative to main frequency, that range will vary with the main
frequency X.
P0.07
Frequency source stacking
selection
1bit
Frequency source selection
00
☆
Main frequency source X
0
Main /auxiliary operation result (10bit
determine operation relationship)
1
Switching between X & Y
2
Switching between X & option 1
3
Switching between Y & option 1
4
10bit
Relationship betweenmain
/auxiliaryfrequency source
Main+auxiliary
0
Main-auxiliary
1
MAX(main frequency source X, auxiliary
frequency source Y)
2
MIN(main frequency source X, auxiliary
frequency source Y)
3
This parameter is used to select frequency setup channel, and of realizing frequency setup through
the compound of main frequency X and auxiliary frequency Y.
1bit
:
Frequency source selection
0
:
Main frequency source X
Main frequency source X is the target frequency.
1
:
Main /auxiliary operation result is targe frequency
,
operation relationship see “10 bit” for details.
2
:
Switching between main frequency source X and auxiliary frequency source Y
When terminal 18 (frequency switching) is invalid, main frequency X is target frequency. On the
contrary, auxiliary frequency Y is the target frequency.
3
:
Switching between main frequency X and main /auxiliary operation result
When terminal 18 (frequency switching) is invalid, main frequency X is target frequency. On the
contrary, auxiliary frequency Y is the target frequency.
4
:
Switching between auxiliary frequency Y and main /auxiliary operation result
When terminal 18 (frequency switching) is invalid, auxiliary frequency Y is the target frequency. On the
contrary, main frequency X is target frequency.
10bit
:
Relationship between main/auxiliary frequency source
0
:
Main frequency auxiliary frequency source Y
Operation result of main + auxiliary is target frequency. It realizes frequency stacking set function.