83
Section V.
Parameter Function Table
It displays the inverter accumulative power consumption.
5.10
Auxiliary function
:
P8.00-P8.53
Code
Description/
Keyboard Display
Setting Range
Factory
Setting
Change
Limit
P8.00
Jog running frequency
0.00Hz~maximum frequency
2.00Hz
☆
P8.01
Jog acceleration time
0.0s~6500.0s
20.0s
☆
P8.02
Jog deceleration time
0.0s~6500.0s
20.0s
☆
It defines the reference frequency and acc. / dec. time of the inverter at the time of jogging.
The jog process is started and stopped according to direct startup mode(P6.00=0)and decelerate to
stop mode(P6.10=0).
P8.03
Acceleration time 2
0.0s~6500.0s
10.0s
☆
P8.04
Deceleration time 2
0.0s~6500.0s
10.0s
☆
P8.05
Acceleration time 3
0.0s~6500.0s
10.0s
☆
P8.06
Deceleration time 3
0.0s~6500.0s
10.0s
☆
P8.07
Acceleration time 4
0.0s~6500.0s
10.0s
☆
P8.08
Deceleration time 4
0.0s~6500.0s
10.0s
☆
HV590 offers 4 groups of speed-up/speed-down time,P0.17/P0.18 and 3 groups above.
P8.03 to P8.08 parameters have the same definition with P0.17 and P0.18.You can switch to choose
the 4 groups through different combination of DI multi-function digital input terminal.For specific using
method,please refer to function code P4.01~P4.05 for details.
P8.09
Hopping frequency 1
0.00Hz~maximum frequency
0.00Hz
☆
P8.10
Hopping frequency 2
0.00Hz~maximum frequency
0.00Hz
☆
P8.11
Hopping frequency amplitude 0.00Hz~maximum frequency
0.00Hz
☆
Fig.5-14 Skip frequency schematicdiagram
When set frequency is within the range of hopping frequency,the actual running frequency will run
close to the set frequency of hopping frequency.Inverter can avoid load mechanical resonance by setting
hopping frequency.
HV590 can set 2 hopping frequency points,if both of them are set to 0,then the hopping frequency
function is canceled.Hopping frequency and hopping frequency amplitude schematic is shown in Fig5-14.
P8.12
Dead zone time of
0.00s~3000.0s
0.0s
☆
Hopping frequency 1
Hopping frequency 2
Output frequency
Hz
Hopping frequency amplitude
t
Hopping frequency amplitude
Hopping frequency amplitude
Hopping frequency amplitude
Summary of Contents for HV590 Series
Page 1: ...HV590 Series Frequency Inverter User Manual HNC Electric Limited ...
Page 189: ......
Page 192: ......