Element
Optional function
Individual
setting
Settings
Setting conditions
Description
EC
Forced thermo ON when
stopping in cooling
operation
O
00
Function disabled
(factory setting)
This function is used to force thermo
ON during 6 minutes when stopping
in cooling operation.
01
Enabled
Ed
Not used
O
00
-
Use at 00 conditions
01
EE
Control in “Automatic”
indoor fan speed mode
O
00
Function disabled
(factory setting)
This function limits the speed of the
indoor fan when room temperature is
close to the setting temperature.
01
Enabled
EF
Control in “Automatic”
indoor fan speed mode
(supporting High H)
Models:
RCI-FSN4
RCIM-FSN4E
RCD-FSN3
RPC-FSN3
RPI-FSN5E
RPI-FSN3E(P)E(-f)
RPIM-FSN4E(-DU)
RPK-FSN(H)3M
O
00
Function disabled
This function limits the speed of the
indoor fan when room temperature
is close to the setting temperature,
allowing to reach High H speed.
01
Function enabled
F0
Not available
–
“- -”
permanent –
–
F1
Automatic OFF timer
setting
Models:
RCI-FSN4
RPC-FSN3
RPK-FSN3M
RPI-FSN5E
RPIM-FSN4E(-DU)
RCD-FSN3
RCIM-FSN4E
RPI-FSN3(P)E
X
00
Function disabled
(Factory setting)
This function sets an automatic OFF
timer to switch OFF the indoor units
controlled by the remote control
switch (when the units have been
started by remote control).
(Do not set the values "0C"-"0F" when
two remote control switches are used
in the same remote control group)
01
1 hour
02
2 hours
03
3 hours
04-24
(04-24) hours
0A
30 minutes
0B
90 minutes
0C
40 minutes
}
Do not set these
when two wired
controllers are
used.
0D
45 minutes
0E
50 minutes
0F
55 minutes
Automatic OFF timer
setting
Models:
RPF(I)-FSN2E
X
00
Function disabled
(Factory setting)
This function is used to set the
automatic timer to switch off when
the unit has been started by remote
control.
01
1 hour
02
2 hours
03
3 hours
04-24
(04-24) hours
0A
30 minutes
0B
90 minutes
F2
Remote control main-
sub setting
X
00
Main (Master remote control)
(Factory setting)
This function is used to define which
remote control switch is used as
master or slave, when two remote
controllers are connected to one
indoor unit.
01
Sub (Slave remote control)
TEST RUN MENU
PMML0496 rev.1 - 12/2020
16