ENGLISH
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
b8
Automatic COOL/HEAT
operation
X
00
Function disabled (factory setting)
This function enables the selection of
Auto cool/heat operation mode. If the
function is not activated, Auto cool/
heat mode cannot be selected on the
remote control switch.
01
Function enabled
b9
Locking of fan speed
setting
X
00
Function disabled
(factory setting)
This function prevents the
modification of the fan speed of the
unit from the remote controller and
from central controls, once it has
been selected.
01
Function enabled
bA
Not available
X
“- -”
permanent Not available
–
bb
Cooling setting
temperature correction
O
00
No compensation (factory setting)
This function decreases the setting
temperature and is used to produce
longer cooling periods.
01
Setting temperature decreased by
1 ºC
02
Setting temperature decreased by
2 ºC
bC
Not used
–
00
-
Use at 00 conditions
01
bd
Not used
–
00
-
Use at 00 conditions
01
bE
Not used
–
00
-
Use at 00 conditions
01
C1
Not used
–
00
-
Use at 00 conditions
01
C2
Not available
–
“- -”
permanent
-
–
C3
Not used
–
00
-
Use at 00 conditions
01
C4
Drain pump operation in
heating mode
O
00
Function disabled
(factory setting)
This function is used to activate the
drain pump in heating mode. Only for
models with drain pump.
01
Function enabled
C5
Static pressure selection
Models
RPI-FSN5E
RPIM-FSN4E(-DU)
RPI-FSN3(P)E(-f)
O
00
Standard static pressure
(factory setting)
This function is used to change the
static pressure of the RPI units from
the remote control.
01
High static pressure
02
Low static pressure
Increase of fan speed
during normal operation
(not during heating
thermo OFF)
Models
RCI-FSN4
RCIM-FSN4E
RCD-FSN3
RPC-FSN3
RPK-FSN(H)3M
RPF(I)-FSN2E
O
00
Standard
(factory setting)
This function is used to change the
fan speed of indoor units installed in
high ceilings.
01
Hi Speed 1
02
Hi Speed 2
Fan speed setting on the remote controller
C5
High H
High
Medium
Low
0
Hi2
Hi
Me
Lo
1
Hi2
Hi1
Hi
Me
2
Hi2
Hi2
Hi1
Hi
C6
Increase of fan speed at
heating thermo OFF
O
00
Function disabled
(factory setting)
This function is used to increase
the fan speed when the thermostat
reaches the set temperature in
heating according to the setting of
function C5.
01
Function enabled