ENGLISH
6.7 ADDRESS CHECK OPERATION
This function is used to check the relation between the indoor
unit and Indoor Unit address. This operation is effective when
multiple indoor units are connected to the remote control switch
and address of the certain unit is unknown.
1
Press and hold “ ” (menu) and “
?
/
” (return / help)
simultaneously for at least 3 seconds during the normal
mode (when unit is not operated). The test run menu will be
displayed.
2
Select “Address Check Operation” from the test run menu
pressing “
” and “OK”.
ADJ
/
OK
Test Run Menu
Indoor Unit Address Change
Address Check Operation
Address Initialization
Setting Initialization
Main Remote Setting
02
03
Entr
Rtrn
Sel.
3
Select the indoor unit by pressing “ ”.
ADJ
Address Check Operation
ON
Rtrn
Sel.
01-01
01-02
01-03
01-04
02-01
02-02
02-03
02-04
03-01
03-02
03-03
03-04
04-01
04-02
04-03
04-04
4
To start operation of the indoor unit selected in (3) press “
”
(ON/OFF).
To return to (3) screen press “ ” (ON/OFF) while indoor
units is operated.
*Repeat (3)-(4) until desired indoor unit address is confirmed.
5
To return to the test run menu press “
?
/
” (return / help)
while indoor unit is not operated.
Confirm the selected indoor unit address and go to “Indoor
Unit Address Change”.
?
N O T E
• “Address Check Operation” is not available when the control of 2
remote control switches (main and sub) are used.
• The switch operation other than “Run/Stop” is not available while
“Address Check Operation” is performed.
• Do not operate from the central controlling devices while “Address
Check Operation” is performed by the remote control switch.
• This function should not be used if there is a Central Control (like
CSNET WEB) in the H-LINK line.
6.8 ADDRESS INITIALIZATION
This function initializes the indoor unit address that has been
changed by “Indoor Unit Address Change” function or set by the
automatic address allocation.
Initializing the address by this function, indoor unit address will
be changed to the dip switch setting.
1
Press and hold “ ” (menu) and “
?
/
” (return / help)
simultaneously for at least 3 seconds during the normal
mode (when unit is not operated). The test run menu will be
displayed.
ADJ
/
OK
Test Run Menu
Indoor Unit Address Change
Address Check Operation
Address Initialization
Setting Initialization
Main Remote Setting
02
03
Entr
Rtrn
Sel.
2
Select “Address Initialization” from the test run menu
pressing “
” and “OK”.
3
Select the indoor unit by pressing “ ” and press
“OK”. The confirmation screen will be displayed.
*Indoor units which are not supporting “Address Initialization”
function can not be selected.
The address of indoor unit that does not support “Address
Initialization” function will not be initialized even when “All” is
specificated.
ADJ
Address Initialization
Rtrn
Sel.
01-01
01-02
01-03
01-04
02-01
02-02
02-03
02-04
03-01
03-02
03-03
03-04
04-01
04-02
04-03
04-04
OK
Entr
4
Select “Yes” and press “OK” to start the address initialization
process.
*If the address initialization is successfully completed,
connection check will be started automatically.
OK
Initialize address?
Address Initialization: All
Yes
No
Sel.
Entr
Rtrn
TEST RUN MENU
PMML0496 rev.1 - 12/2020
29