Element
Optional function
Individual
setting
Settings
Setting conditions
Description
rb
Minimum operation time
to allow the change of
operation mode in auto
cooling/heating mode
with dual set point
X
00
Disabled
This function is used to define a
minimum time of operation in a given
mode, in order to avoid too frequent
changes of operation mode.
Operation mode does not change
until the minimum transition time
passes, even if the room temperature
reaches the setpoint to shift to the
other operation mode.
01
10 minutes
02
20 minutes
03
30 minutes
04
40 minutes
05
50 minutes
06
60 minutes
07
70 minutes
08
80 minutes
09
90 minutes
10
100 minutes
11
110 minutes
12
120 minutes
rC
Maximum outdoor
temperature to allow
operation mode switch
to heating in auto
cooling/heating with dual
set point
X
00
Disabled
If outdoor ambient temperature is
higher than rC, there is no mode
transition to heating in automatic
cooling/heating operation mode,
even if room temperature reaches
the setpoint to switch operation mode
from cooling to heating.
01
20.0 ºC
02
21.0 ºC
03
22.0 ºC
·
·
·
·
·
·
21
40.0 ºC
22
0.0 ºC
23
1.0 ºC
24
2.0 ºC
·
·
·
·
·
·
41
19.0 ºC
rd
Minimum outdoor
temperature to allow
operation mode switch
to cooling in auto
cooling/heating with dual
set point
X
00
Disabled
If outdoor ambient temperature is
lower than rd, there is no mode
transition to cooling in automatic
cooling/heating operation mode,
even if room temperature reaches
the setpoint to switch operation mode
from heating to cooling.
01
10.0 ºC
02
11.0 ºC
03
12.0 ºC
·
·
·
·
·
·
31
40.0 ºC
32
-20.0 ºC
33
-19.0 ºC
34
-18.0 ºC
·
·
·
·
·
·
61
9.0 ºC
rE
Temperature for the
beginning of heating in
setback
X
00
15.0 ºC
If room temperature becomes lower
than this setting, indoor unit operation
is resumed in heating mode by the
setback function.
01
16.0 ºC
02
17.0 ºC
03
18.0 ºC
04
19.0 ºC
05
10.0 ºC
06
11.0 ºC
07
12.0 ºC
08
13.0 ºC
09
14.0 ºC
TEST RUN MENU