ENGLISH
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
qE
Setback mode
X
00
Always
When selecting “01: Input”, it is
necessary to set up one input contact
(i1 or i2) with the setback function
“09”. This operation has to be done in
the input/output setting menu of the
remote controller.
When selecting “02: Schedule” or
“03: Manual”, additional settings are
required.
01
Input
02
Schedule
03
Manual
qF
Operation state after the
end of setback operation
X
00
Stop
Operation state to switch to upon the
end of setback duration.
01
Run
02
Operation state before the
beginning of setback
r1
Dual setpoint
X
00
Function disabled
(factory setting)
This function allows the setting of
independent setpoints for cooling
and heating in the automatic cooling/
heating mode.
01
Function enabled
r2
Setting of temperature
differential for switching
cooling and heating
X
0.5
0.5 ºC
This function can only be set when
function r1 is set to 01.
1.0
1.0 ºC
1.5
1.5 ºC
2.0
2.0 ºC
2.5
2.5 ºC
3.0
3.0 ºC
r3
Not used
-
0.5
-
Not used
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
r4
Not used
-
00
-
Use at 00 conditions
01
r5
Not used
-
00
-
Use at 00 conditions
01
r6
Not used
-
00
-
Use at 00 conditions
01
r7
Not used
-
00
-
Use at 00 conditions
01
r8
Not used
-
00
-
Use at 00 conditions
01
r9
Remote control
prohibition during
setback operation
X
00
Start/Stop allowed (Factory setting)
Manual run/stop from the remote
controller can be disabled during
setback operation.
This function is fixed to 00 (Disabled)
when function qE is set to 00
(Always).
01
Start/Stop not allowed
!
WA R N I N G :
Blocking of Start/Stop shall never
be set due to safety concerns.
02
Only Stop allowed
rA
Not used
-
00
-
Use at 00 conditions
01
02
03
04
05
06
07
TEST RUN MENU
PMML0496 rev.1 - 12/2020