ENGLISH
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
E2
KPI: Increase of air
supply volume
O
00
Disabled function
(factory setting)
This function is used to increase the
air supply pressure in the room.
01
Enabled function
Econofresh enthalpy
sensor
00
Disabled function
(factory setting)
This function selects the enthalpy
sensor input for Econofresh.
01
Enabled function
E3
Not used
–
00
-
Use at 00 conditions
01
E4
KPI: Pre-cooling / pre-
heating period
O
00
Disabled (factory setting)
This function delays unit startup with
energy recovery
01
30 minutes
02
60 minutes
Econofresh: CO2 sensor
00
Disabled (factory setting)
This function selects the CO2 gas
sensor input for Econofresh.
01/02
CO2 sensor
(required setting E1=00)
E5
Not used
–
00
-
Use at 00 conditions
01
E6
Period of indoor fan
operation after cooling
operation stoppage
O
00
Disabled function
(factory setting)
This function prevents the
condensation in the unit by keeping
the fan running after the unit
operation has been turned OFF.
01
60 minutes
02
120 minutes
E7
Not used
–
00
-
Use at 00 conditions
01
E8
Control for stop of the
indoor unit fan during
heating thermo OFF
conditions (with remote
sensor THM-R2AE
connected to the THM4
connector in the indoor
unit PCB)
O
00
Fan operation in Low speed
This function stops the fan to prevent
cold draughts or overheating.
C8 must be set to 01 to use the
E8=01 setting.
The connection of a THM-R2AE
remote temperature sensor to the
THM4 port in the indoor unit PCB
is required. The remote sensor
shall be installed in a proper place
for the correct detection of room
temperature.
(In case that automatic louvre is
set, the louvre will keep operating
in both thermo ON and thermo OFF
condition.)
01
Fan stop in thermo OFF conditions.
E9
Intermittent fan
operation in heating stop
Not available for models:
RPF(I)-FSN2E
O
00
Function disabled
(factory setting)
In case that indoor unit operation is
set OFF by the remote control switch,
under certain conditions the fan is
operated in cycles consisting of 3
minutes of operation at SLow speed
and 30 minutes of stoppage.
01
Function enabled
EA
Not used
–
00
-
Use at 00 conditions
01
02
Eb
Indoor unit fan control
during cooling thermo
OFF conditions
O
00
Function disabled
(factory setting)
This function decreases speed of the
indoor unit fan during cooling thermo
OFF, to reduce the spread of smells
and humidity.
01
Low
02
Slow
TEST RUN MENU
PMML0496 rev.1 - 12/2020
15