ENGLISH
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
F3
Automatic reset of
setting temperature
X
00
Function disabled
(Factory setting)
This function is used to limit unit
operation and save energy.
The setting temperature is
automatically set to the value defined
with functions "F5" or "F6", according
to the current operation mode, after
the time set with function "F4" has
passed since the last manual change
of setting temperature.
In case that the values of "F5" or "F6"
are out of the limits set with functions
"FC" and "Fd", limitations set by "FC"
and "Fd" have priority.
01
Function enabled
F4
Automatic reset time
X
00
30 minutes (factory setting)
This function sets the automatic reset
time delay for function F3.
01
15 minutes
02
60 minutes
03
90 minutes
F5
Automatic reset
temperature for cooling
X
19
19 °C
This function defines the default
temperature set point for the
automatic reset function F3 in FAN/
COOL/DRY modes.
20
20 °C
21
21 °C
·
·
·
·
·
·
24
24 °C
25
25 °C (factory setting)
26
26 ºC
·
·
·
·
·
·
28
28 ºC
29
29 ºC
30
30 ºC
F6
Automatic reset
temperature for heating
X
17
17 ºC
This function defines the default
temperature set point for the
automatic reset function F3 in HEAT
mode.
18
18 ºC
·
·
·
·
·
·
20
20 ºC
21
21 ºC (factory setting)
25
25 ºC
·
·
·
·
·
·
28
28 ºC
29
29 ºC
30
30 ºC
F7
Prevention of operation
stoppage due to wrong
operation of the remote
controller
X
00
Function disabled
(factory setting)
Operation is stopped by pressing the
run/stop switch for 3 seconds.
01
Function enabled
F8
Lock function for
operation mode
selection
X
00
Function disabled
This function is used to prevent
changes to the operation mode.
01
Function enabled
(factory setting)
F9
Lock function for
temperature setting
X
00
Function disabled
This function is used to prevent
changes to the temperature setting.
01
Function enabled
(factory setting)
FA
Lock function for fan
speed selection
X
00
Function disabled
This function is used to prevent
changes to the fan speed.
01
Function enabled
(factory setting)
Fb
Lock function for swing
louvre operation
X
00
Function disabled
This function is used to prevent
changes to the automatic louvre
operation.
01
Function enabled
(factory setting)
TEST RUN MENU
PMML0496 rev.1 - 12/2020