Element
Optional function
Individual
setting
Settings
Setting conditions
Description
P6
Operation of the ECO
button
X
00
ECO button enabled (factory
setting)
The operation of ECO button is
disabled when P6 is set to 01
01
ECO button disabled
P7
Prohibition of menu
screen transition
X
00
Function disabled
(factory setting)
This function is used to prohibit the
access to the menu screens.
The text "Display disabled" appears
on screen instead.
01
Function enabled
P8
Not used
-
00
-
Use at 00 conditions
01
P9
Not used
-
00
-
Use at 00 conditions
01
PA
Daylight saving time
X
00
1 hour
This function is used to set the
amount of adjustment when daylight
saving time is applied.
01
2 hours
Pb
Not used
-
00
-
Use at 00 conditions
01
PC
Not used
-
00
-
Use at 00 conditions
01
q1
Not used
-
00
-
Use at 00 conditions
01
q2
Not used
-
-
-
Not used
q3
Not used
-
-
-
Not used
q4
Not used
-
-
-
Not used
q5
Not used
-
-
-
Not used
q6
Not used
-
00
-
Use at 00 conditions
01
q7
Not used
-
00
-
Use at 00 conditions
01
q8
Not used
-
00
-
Use at 00 conditions
01
q9
Not used
-
00
-
Use at 00 conditions
01
qA
Not used
-
00
-
Use at 00 conditions
01
qb
Operation mode with
setback
X
00
Disabled
Operation modes in which setback
operation is activated to keep a
minimum comfort in the room while it
is not occupied.
01
Cooling
02
Heating
03
Cooling/Heating
qC
Temperature differential
for the setback function
X
00
2.0 ºC
Target temperatures for both cooling
and heating operation are determined
versus a temperature to start setback
operation (rE, rF)
Target temperature calculation:
Target temperature in cooling mode:
rF - qC (°C)
Target temperature in heating mode:
rE + qC (°C)
01
3.0 ºC
02
4.0 ºC
03
5.0 ºC
04
1.0 ºC
qd
Minimum stop time of
setback
X
00
10 minutes
To avoid the frequent activation
of setback operation, a minimum
off-time shall pass from the end of
setback operation until the beginning
of the following setback operation.
Even if room temperature reaches the
setpoint to start setback operation,
setback operation does not start until
the minimum off-time has expired.
01
20 minutes
02
30 minutes
03
40 minutes
04
50 minutes
05
60 minutes
06
70 minutes
07
80 minutes
08
90 minutes
09
100 minutes
10
110 minutes
11
120 minutes
TEST RUN MENU
PMML0496 rev.1 - 12/2020
22