ENGLISH
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
rF
Temperature for the
beginning of cooling in
setback
X
00
26.0 ºC
If room temperature becomes higher
than this setting, indoor unit operation
is resumed in cooling mode by the
setback function.
01
27.0 ºC
02
28.0 ºC
03
29.0 ºC
04
30.0 ºC
05
31.0 ºC
06
32.0 ºC
07
33.0 ºC
08
34.0 ºC
09
35.0 ºC
10
25.0 ºC
S1
Not used
-
00
-
Use at 00 conditions
01
S2
Not used
-
00
-
Use at 00 conditions
01
S3
Not used
-
00
-
Use at 00 conditions
01
S4
Not used
-
00
-
Use at 00 conditions
01
S5
Not used
-
00
-
Use at 00 conditions
01
S6
Not used
-
00
-
Use at 00 conditions
01
02
S7
Not used
-
00
-
Use at 00 conditions
01
02
03
04
05
06
07
S8
Not used
-
00
-
Use at 00 conditions
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
?
N O T E
• O: allows for individual setting.
• X: the setting is made for all outdoor units.
• –: not used.
?
N O T E
• The changes to the optional function settings must be done after 3
minutes have passed since start-up.
• It is recommended to keep track of the changes made to optional
function settings, for further reference.
• The available optional settings are different depending on the indoor
and outdoor unit models. Check the technical documentation of the
indoor and outdoor units to ensure whether the optional settings are
available for these units.
• The optional functions with “X” mark at the individual setting column
can change the condition only when “All Rooms” is set.
• The following optional functions are disabled when RPI units with
Econofresh are installed: b7, bA, bd, bE, C1, C2, C3, C9, CA, Cd, CF,
d6, E3, E5, E7, E9, EA, FE, FF, H1, H3, H4, J2, J4, J7, J8, J9, JA, JB,
K1, K2, K3, K4, K5.
• The listed optional functions are valid for the following models:
Indoor Unit series
With software number
RCI-(1.0~6.0)FSN4
P-4736
RCIM-(0.4~2.5)FSN4E
P-4729
RCD-(0.8~6.0)FSN3
P-4729
RPK-(0.4~4.0)FSN(H)4M
P-4725
RPI-(0.4~1.5)FSN5E
P-4725
RPI-(2.0~3.0)FSN5E
P-4725
RPI-(4.0~6.0)FSN5E
P-4735
RPIM-(0.6~1.5)FSN4E
P-4735
RPC-(1.5~6.0)FSN3
P-4736
TEST RUN MENU
PMML0496 rev.1 - 12/2020
25