2 Unit installation
RPF - Floor type, RPFI - Floor concealed type
SMGB0099 rev.0 - 12/2016
65
2
Install a service hatch near the pipe connection area and electrical junction box for installation and maintenance work.
Unit (inside)
Floor
Service
access panel
Service
access panel
Model
A (mm)
B (mm)
RPF
RPFI
RPF
RPFI
RPF(I)-1.0FSN2E
630
620
1479
1359
RPF(I)-1.5FSN2E
RPF(I)-2.0FSN2E
1729
1609
RPF(I)-2.5FSN2E
Check that the drain hose can be installed maintaining the necessary down-slope.
Installation
!
C A U T I O N
The place where the indoor unit is to be installed must be a flat surface with enough space to fully house the unit. The weight of the unit
must be evenly distributed over the surface.
Handle and position the unit carefully.
Check that the attachment position (in mm) of the unit is as indicated in the figure.
Model
A
B
C
D
E
F
G
RPF-1.0FSN2E
1045
754
217
732
228
140
360
RPF-1.5FSN2E
1170
879
857
228
140
630
RPFI-1.5FSN2E
988
879
66
857
77
138
620
RPF-2.0FSN2E
1420
1129
11
1107
228
140
630
RPF-2.5FSN2E
RPFI-2.0FSN2E
1234
1129
11
1107
53
139
620
RPFI-2.5FSN2E
Adjust the horizontal level of the unit by loosening or tightening the unit installation bolts.
Check that the condensate discharge system in the unit works correctly. To do so, check the level of the drain pan using
a spirit level. The side of the unit on which the drain hose is located must be around 3 mm lower than the opposite side.
Secure the base plate and the rear plate of the unit using field-supplied bolts and screws.
?
N O T E
RPFI units: remove the electrical wiring box when fitting the installation bolts.