2 Unit installation
RCD - 2-way cassette
SMGB0099 rev.0 - 12/2016
40
!
C A U T I O N
•
To avoid damaging the panel, the long screws securing it are fitted with
stops to stop tightening at the set position.
• Where the air panel does not reach the ceiling surface or in the event of air
leaks on the touching surface, readjust the installation height of the indoor
unit.
Check that there are no gaps in the touching surface between
the indoor unit and the air panel. Gaps may cause air leaks or
condensation.
P-N46DWA
Indoor unit
Long screw (A) x4
(M6x50)
Long screw (B) x4 (M6x60), only
for P-N46DWA
Considerations following air panel installation
!
C A U T I O N
Do not move the air louver by hand. The drive mechanism may be damaged.
Air louver
Electrical connection of the air panel
!
C A U T I O N
Switch off the power supply to the unit before coupling the connectors, otherwise the automatic louver will not work.
The following connector is used with the air panel (see from the lower surface of the air panel without the air inlet grille).
Hook
Electrical box
of indoor unit
Outlet for electrical wiring
Without air intake grille
Couple the connectors as indicated in the figure (view of the electrical box from above).
Connector for auto swing motor
(low voltage 7 pin, RED) (CN17)
Outlet for
electrical wiring
Electrical box
of indoor unit
Printed circuit
board (PCB)