2 Unit installation
RPI(M) - Ducted indoor unit (0.6-6.0)FSN4E(-DU)
SMGB0099 rev.0 - 12/2016
49
2
Before starting installation, plan the direction of the pipes and wiring required. Also bear in mind that there must be
enough space around the unit for installation and maintenance.
Check that the ceiling surface where the unit is to be installed is completely horizontal.
Check that the drain hose can be installed maintaining the necessary down-slope.
Installation
Install the M10 (3/8) suspension bolts depending on the type of surface:
Steel beams
Wooden beams
Concrete beams
Steel beam
Anchor bolt
(W3/8 or M10)
:RRGHQ%HDP
:RRGHQ%DU
PPWRPP
VTXDUH
Wooden beam
Wooden bar
(60mm to 90mm square)
1
2
3
4
5
1 150 to 160 mm
2 Steel
3 Anchor bolt (W3/8 or M10)
4 Concrete
5 Insert (100 to 150 kg)
1 Suspension bolt
2 Suspension bracket
3 Left side
4 Inlet air
5 Washer
6 Nut
7 Right side (service cover)
Thread on the nuts and fit the washers for all the bolts, as shown in the figure.
Fit two suspension brackets onto the nut and washer of each bolt, starting on one side.
Check that the nuts and washers are correctly secured with the suspension bracket retainers and fit the brackets onto
their nuts and washers on the other side.
Bear in mind the position of the side for pipe connection before lifting the indoor unit.
!
C A U T I O N
•
Before lifting the unit, prepare any necessary means (ladders, scaffolding, elevator platform, etc.) and check that the current safety
regulations in the place where the installation is taking place are met.
•
Check that the lifting work can be carried out without the risk of injuries to you or others in the surrounding area.
• Request the assistance of another person to lift the unit.
Check that the condensate discharge system in the indoor unit works
correctly. To do so, check the level of the drain pan using a spirit level
or a clear flexible pipe full of water. The side of the unit on which the
drain hose is located must be around 5 mm lower than the front side.
Condensate drain connection
?
N O T E
The drainage connection on the RPIM unit is located at the rear.