2 Unit installation
Optional accessories
SMGB0099 rev.0 - 12/2016
88
Example of 3-Way Outlet
380
4
3
2
1 (*1)
340
435
470
440
380
340
340
Blocking Part
Piping side
Use
Unuse
Cut off
the corner
Cut off
the corner
RCI-(1.0-1.5)FSN4
RCI-(2.0-6.0)FSN4
Use
Part of Blocking Plate
Example of 2-Way Outlet
The air outlet directions can not be selected other than the figure below. (If other air outlet directions are selected, dew
condensation may occur.)
3 (*2)
2 (*1)
1
Blocking Part
Piping side
RCI-(1.0-6.0)FSN4
Refer to the item (1)
3-Way Outlet
for the size of blocking
plate of each model
*1 Change the position of the outlet temperature thermistor. If not, the room temperature adjustment may not be
available.
*2 In the case of Example 3, the air flow volume will decrease compared with other cases. Set the high speed setting.
Example for 3-Way and 2 Way Outlet
Near the wall: 3-way outlet
In a corner: 2-way outlet
In rectangular room: 2-way outlet
• Near the Wall: 3-Way Outlet
• In a Corner: 2-Way Outlet
• In Rectangular Room: 2-Way Outlet
• Near the Wall: 3-Way Outlet
• In a Corner: 2-Way Outlet
• In Rectangular Room: 2-Way Outlet
• Near the Wall: 3-Way Outlet
• In a Corner: 2-Way Outlet
• In Rectangular Room: 2-Way Outlet