2 Unit installation
RCD - 2-way cassette
SMGB0099 rev.0 - 12/2016
38
Check that the condensate discharge system in the indoor
unit works correctly. To do so, check the level of the drain
pan using a spirit level or a clear flexible pipe full of water.
The side of the unit on which the drain hose is located must
be around 5 mm lower than the other sides.
Adjust 4 corners
of the unit using
clear vinyl tube
with water inside
Clear vinyl tube
Bracket for
panel
Drain pipe
Adjusting the space between the indoor unit and the opening in the false ceiling
a. For installation work, the pattern board is required.
The pattern board for installation and the checking
scale are printed on the back side of the packing.
b. Cut off the checking scale for dimension of opening
from the packing.
Checking scale for
dimension opening
Pattern board
for installation
Packing
(corrugated board)
Adjust the indoor unit to the correct position using the pattern and checking pattern for the installation.
For panelled ceilings
When installing the indoor unit to a false ceiling with an opening, check the dimension of the opening and adjust the
clearance between the Indoor unit and the opening following the indications given in the next illustrations
Attach the scale
to the bottom
side of the unit
Indoor unit
Attach the scale to
the surface of ceiling
Checking scale
Indoor unit
Surface of ceiling
Longer dimension of opening
Shorter dimension of opening
Check the clearance of the 4 sides
between the Indoor unit and the
opening
For ceilings without panels
Dimension for
opening
Dimension for
opening
Pattern board
Suspension bolt
Screw M6
Ceiling surface
Pattern board
Indoor unit
a. When the false ceiling is not yet completed, attach the pattern board to the indoor unit with the M6 screws, as
shown in the figure. And specify the location of the opening. Adjust the position of the indoor unit as the procedure
“For panelled ceilings” after ceiling is completed.
b. Tighten two nuts of each suspension bolt after the adjustment is completed. Apply thread-locking product to the
suspension bolts and nuts in order to prevent them from loosening, otherwise, abnormal noise may be caused by
mechanical vibrations and the indoor unit may become loose.
c. Adjust the indoor unit to the correct position, using the checking scale.