4 Electrical and control settings
Unit electrical wiring and connection
SMGB0099 rev.0 - 12/2016
133
4
4.1.2 Minimum requirements of the protection devices
!
C A U T I O N
•
Ensure specifically that there is an Earth Leakage Breaker (ELB) installed for the units.
•
If the installation is already equipped with an Earth Leakage Breaker (ELB), ensure that its rated current is large enough to hold the
current of the units.
?
N O T E
•
Electric fuses can be used instead of magnetic Circuit Breakers (CB). In that case, select fuses with similar rated values as the CB.
•
The Earth Leakage Breaker (ELB) mentioned on this manual is also commonly known as Residual Current Device (RCD) or Residual
Current Circuit Breaker (RCCB).
•
The Circuit Breakers (CB) are also known as Thermal-Magnetic Circuit Breakers or just Magnetic Circuit Breakers (MCB).
Indoor units
Model
Power supply
Maximum current (A)
CB (A)
ELB
(nº poles/A/mA)
Indoor units (0.6-6.0) HP
1~ 230V 50Hz
or
1~ 220-240V 50Hz
(depending on model)
5.0
6
2/40/30
RPI-(8.0/10.0)FSN3E(-f)
10.0
10
RPI-16.0FSN3PE(-f)
16.2
20
RPI-20.0FSN3PE(-f)
17.7
20
CB: Circuit breaker; ELB: Earth leakage breaker
KPI units
Model
Power source
Maximum current (A)
CB (A)
ELB
(nº poles/A/mA)
KPI-252E4E
1~ 230V50Hz
4.0
6
2/40/30
KPI-502(E/X)4E
4.0
6
KPI-802(E/X)4E
4.0
6
KPI-1002(E/X)4E
8.0
10
KPI-1502E4E
8.0
16
KPI-2002E4E
8.0
16