4 Electrical and control settings
Setting of DIP switches and RSW switches
SMGB0099 rev.0 - 12/2016
162
DSW3: capacity code setting
No settings are required. This DIP switch with 4 or 6 switches (depending on Indoor Units) is used to set the capacity
code corresponding to the power of the indoor unit.
Indoor Unit capacity 1.5 HP, 2 HP and 2.5 HP can be set to a lower capacity (1.3 HP, 1.8 HP and 2.3 HP) using the DIP
switch.
Power (HP)
0.6
0.8
1.0
1.3
(*)
1.5
1.8
(*)
1 2 3 4 5 6
ON
1 2 3 4
5 6
ON
1 2 3 4
5 6
ON
1 2 3 4
5 6
ON
1 2 3 4
5 6
ON
1 2 3 4
5 6
ON
Power (HP)
2.0
2.3
(*)
2.5
3.0
4.0
1 2 3 4
5 6
ON
1 2 3 4
5 6
ON
1 2 3 4
5 6
ON
1 2 3 4
5 6
ON
1 2 3 4
5 6
ON
Power (HP)
5.0
6.0
8.0
10.0
1 2 3 4
5 6
ON
1 2 3 4
5 6
ON
1 2 3 4
ON
1 2 3 4
ON
Power (HP)
16.0
20.0
PCB1
(Upper Ebox)
1 2 3 4
ON
1 2 3 4
ON
PCB2
(Lower Ebox)
1 2 3 4
ON
1 2 3 4
ON
?
N O T E
•
(*)
Capacity available with DSW3 setting.
•
In those model with switch number 5 and 6, both switches are not used (except 0.6 HP models)
DSW4: unit model code setting
No settings are required. This DIP switch is used to set the model code corresponding to the type of indoor unit.
Unit model
RCI-FSN4
RCIM-
FSN4(E) RCD-FSN3 RPC-FSN3E RPC-FSN3 RPI-FSN4E RPI-FSN3E
(-f)
RPI-FSN3PE(-f) RPIM-FSN4E RPF(I)-FSN2E
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
?
N O T E
DSW4 Not assembled in the RPK-FSN(H)3M models.