9 Servicing
RPI-(0.6-6.0)FSN4E - Ducted indoor unit
SMGB0099 rev.0 - 12/2016
294
9.6.6
Removal of the float switch
?
N O T E
To disconnect and remove the float switch, previously see the chapter
corresponding to the wiring diagrams in this Manual.
1 Remove the drain pump support screws and remove it.
2
Loosen the screws securing the float switch to the
support.
3
Loosen the resin nut securing the float switch and
remove it.
Nº
Part
1
Float switch position
?
N O T E
The torque value of the resin nut is 0.3 - 0.4 Nm. If the torque value
is higher, the nut will be damaged.
Nº
Part
1
Float switch
9.6.7
Removal of the air filter
Nº
Part
1
Air filter
2
Screws
3