4 Electrical and control settings
Unit electrical wiring and connection
SMGB0099 rev.0 - 12/2016
132
4.1 Unit electrical wiring and connection
!
C A U T I O N
Check to ensure that the field supplied electrical components (mains power switches, circuit breakers, wires, connectors and wire
terminals) have been properly selected according to the electrical data indicated on this chapter and they comply with national and local
codes. If it is necessary, contact with your local authority in regards to standards, rules, regulations, etc.
4.1.1 Wiring size
Use wires which are not lighter than the polychloroprene sheathed flexible cord (code designation 60245 IEC 57).
Indoor units
Model
Power supply
Maximum current
(A)
Power supply cable size
EN60 335-1
Transmitting cable size
EN60 335-1
Indoor units (0.6-6.0) HP
1~ 230V 50Hz
or
1~ 220-240V 50Hz
(depending on
model)
5.0
2 x 0.75 mm
2
+GND
2x 0.75 mm
2
RPI-(8.0/10.0)FSN3E(-f)
10.0
2 x 1.5 mm
2
+GND
RPI-16.0FSN3PE(-f)
16.2
2 x 4.0 mm
2
+GND
RPI-20.0FSN3PE(-f)
17.7
KPI units
Model
Power supply
Maximum current
(A)
Power supply cable size
EN60 335-1
KPI-252E4E
1~ 230V 50Hz
4.0
2 x 1.0 mm
2
+GND
KPI-502(E/X)4E
4.0
2 x 1.0 mm
2
+GND
KPI-802(E/X)4E
4.0
2 x 1.0 mm
2
+GND
KPI-1002(E/X)4E
8.0
2 x 1.5 mm
2
+GND
KPI-1502E4E
8.0
2 x 2.5 mm
2
+GND
KPI-2002E4E
8.0
2 x 2.5 mm
2
+GND
DX-Interface
Model
Power supply
Maximum current
(A)
Power supply cable size
EN60 335-1
EXV-(2.0-10.0)E2
1~ 230V 50Hz
5.0
2 x 0.75 mm
2
+GND