6 Optional functions
Optional functions through Remote control
SMGB0099 rev.0 - 12/2016
213
6
Elem.
Optional function
Individual
setting
Settings
Setting conditions
Description
EA
Not available
O
00
Not available
Use at 00 conditions
–
01
Eb
Fan operation control at
cooling Thermo-OFF
O
00
Not activated function
This function decreases the unit fan
speed to reduce the spreading of
smells and humidity.
01
Low
02
Slow
EC
Forced Thermo-ON
stoppage at cooling
O
00
Not activated function
This function is used to force
stoppage when cooling is complete.
01
Available
Ed
Not available
O
00
Not available
Use at 00 conditions
–
01
EE
Automatic fan speed
control
O
00
Not activated function
This function limits the unit operation
by automatically controlling the fan
speed when the room temperature is
close to the set temperature.
01
Activated function
EF
Automatic indoor fan
speed mode (supporting
High H)
Models
RPI-FSN4E
RPIM-FSN4E(-DU)
RCD-FSN3
RCIM-FSN4(E)
O
00
Not activated function
01
Activated function
F0
Not available
-
-
Not available
F1
Automatic OFF timer
setting
Models
RCI-FSN4
RPC-FSN3
RPK-FSN3M
RPI-FSN4E
RPIM-FSN4E(-DU)
RCD-FSN3
RCIM-FSN4(E)
X
00
Not activated function
This function is used to set the
automatic timer to switch off when
the unit has been started by remote
control.
(Do not set the functions "0C"-"0F"
when two remote control switches
are used in the same remote control
group)
01
1 h
02
2 h
03
3 h
04-24
(04-24) h
0A
30 min
0B
90 min
0C
40 min
0D
45 min
0E
50 min
0F
55 min
Automatic OFF timer
setting
Models
RPI-FSN3(P)E
RPC-FSN3E
RPF(I)-FSN2E
X
00
Not activated function
This function is used to set the
automatic timer to switch off when
the unit has been started by remote
control.
01
1 h
02
2 h
03
3 h
04-24
(04-24) h
0A
30 min
0B
90 min
F2
Remote control main/sub
setting
X
00
Main (Master Remote Control)
This function is used when two
remote controls are installed in a
system.
01
Sub (Slave Remote Control)
F3
Automatic reset of setting
temperature
(4)
X
00
Not activated function
This function releases the fixed
temperature setting after a certain
time to limit unit operations and save
energy.
01
Activated function
F4
Automatic reset time
X
00
30 minutes
(factory setting)
This function is used to set the
automatic reset time with the
temperature setting
01
15 minutes
02
60 minutes
03