77
PW3335A985-01
Set and Query
:MEASure?
Output Items
(Measurement status data: instantaneous value, maximum value, minimum value)
Syntax
Instantaneous
value
:
MEASure[:NORMal]:ITEM:STATus:INST(?)
<Output item>
Maximum/Minimum
value
:MEASure[:NORMal]:ITEM:STATus:MAXmin(?) <Output item>
Response
<Output item (NR1)>
128
64
32
16
8
4
2
1
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
STATUS
Description
Sets the measurement data status (instantaneous value, maximum value,
minimum value) output items as numerical values between 0 and 1.
Although NRf numerical values are accepted, values to the right of the decimal are
dropped.
If no items are specified directly via a
:MEASure?
query, output is based on the
specification of this command.
INST indicates the status for the instantaneous value at the time when the data is
acquired.
MAXmin indicates the total from the time the maximum and minimum values were
last reset.
The Status data indicates the status of the warning indicators on the instrument
when the measurement data was saved. The Status data is represented by a
32-bit hexadecimal value. The content of each of these 32 bits is as follows:
bit31 bit30 bit29 bit28 bit27 bit26 bit25 bit24
-
-
-
HM
-
-
-
RP
bit23 bit22 bit21 bit20 bit19 bit18 bit17 bit16
-
-
-
CP
-
-
-
SY
bit15 bit14 bit13 bit12 bit11 bit10
bit9
bit8
-
-
-
RI
-
-
-
RU
bit7
bit6
bit5
bit4
bit3
bit2
bit1
bit0
-
-
-
PI
-
-
-
PU
HM:
Harmonic wave measurement synchronization error
RP:
Active power range exceeded
CP:
Instrument protection mode activated
SY:
Synchronization error
RI:
Current range exceeded
RU:
Voltage range exceeded
PIx:
Current peak exceeded
PUx:
Voltage peak exceeded
Example
Command
:MEAS:ITEM:STAT:INST 1
Specifies to turn ON measurement status output.
Query
:MEAS:ITEM:STAT:INST?
Response
(When HEADER ON)
:MEASURE:NORMAL:ITEM:STAT:INST 1
(When HEADER OFF)
1