The following cables generally connect the SpeedStile BP DS:
Power Supply Cable
For each door a power supply cable with 3 conductors
must be used, starting from the user switch gear and
running to the power supply unit terminal block (Phase,
Neutral and PE conductors).
Double insulation cables shall be used. The conductors'
section must be determined according to the cable
length and the power required. At least 0.75 mm2
(AWG18) section is recommended.
Remote Control
If there is a remote control panel, an electric shielded
cable with eight (8) Line conductors must be provided
for each gate, running from the logic board to
the remote control panel. It includes the Emergency /
Fire Alarm command.
The conductor section, must be determined according to the length L of the cable:
if L < 100 m use 0.33 mm2 (AWG22);
if 100 m < L < 250 m use 0.5 mm2 (AWG20);
if 250 m < L < 500 m use 0.8 mm2 (AWG18).
Emergency / Fire Alarm
If there is not the remote control but only the fire alarm
command is needed, an electric shielded cable with two
(2) conductors must be provided.
For the conductor section, follow the same rules
described for the remote control line.
Serial Communication Line
If the RS485 serial connection is provided (optional), the
logic boards of each barrier must be connected one after
the other with a data transmission cable.
A twisted and shielded cable (FTP Cat. 5) should be used
or the connection.
The cable must be posed in independent canalization
and the recommended maximal length is 500 m.
Badge Reader Connection Line
The customer should consult the data provided by the
reader’s system supplier.