TSA 160 NT
40
Commissioning and service
21 Commissioning and service
Commissioning and service can be carried out with the display programme switch DPS, the service terminal
ST220 or using the push buttons S1 and S2.
à
Parameter setting using the buttons S1 and S2 of the control see chapter 24.2, “Service buttons S1 and S2”.
à
In case of parameter setting of the control using the push buttons S1 and S2, the RS485 connection between
the active leaf and passive leaf control can remain.
à
In case of parameter setting using the ST220 the active leaf and passive leaf configurations have to be carried
out separately. Then the drives can be configured with an existing bus connection.
à
In case of parameter setting of the control with DPS, the RS485 connection between the active leaf and passive
leaf control has to be disconnected.
21.1 Pre-conditions
à
Assembly is complete (see assembly and service instructions for the drive).
à
Electrical installation is complete.
à
Sensors are correctly configured and aligned.
à
Internal programme switch at the active and passive leaf drive set to 0 (NIGHT/OFF).
à
If available, external programme switch MPS or MPS-D set to NIGHT operating mode.
21.2 Carrying out commissioning
21.2.1 Preparation
For the ST220 push button functions, see chapter 23.2, “Operation of ST220”.
For DPS and S1, S2 push button functions, see 24, “Display programme switch DPS and Service push buttons S1, S2”.
X
Switch off the mains power supply of the drive.
X
Disconnect the RS485 connection to the active and passive leaf control (connector RS458/ASF or connector RS485).
X
If necessary remove TPS and connect DPS to the active leaf control.
X
Switch on the mains power supply of the drive.
21.2.2 Commissioning with ST220
Configuring a brand-new 1-leaf drive
In the menu “Door parameters”:
à
In the submenu “Number of leaves”: “1-leaf drive”.
à
In the menu “Type of installation”: “Electric strike type“
à
In the menu “Signals”, submenu “Input signals”:
à
“SI1 – terminal SIS”, “SI1 contact type”
à
“SI1 – terminal SIS”, “SI1 function”
à
“SI3 – terminal SIO”, “SI3 contact type”
à
“SI3 – terminal SIO”, “SI3 function”
à
In the menu “Signals”, submenu “Output signals”: “Testing SI”
X
Set further parameters if appropriate (see chapter 23.5, “Service menu ST220”), in particular “Drive type”,
“Type of installation” Type of bolt contact”.
Configuring a brand-new 2-leaf drive
X
Switch the mains supply voltage off.
X
Set the internal programme switch at the active leaf drive to “II AUT” or, if available, the MPS-D to “Automatic”.
X
Disconnect the RS485 connection active leaf control – passive leaf control.
X
Connect the service terminal ST220 to the active leaf control.
X
Switch on the 230 V mains supply voltage.
X
With TSA 160 NT F press the reset switch.
à
In the menu “Door parameters”, submenu “Number of leaves”: “2-leaf active” for active leaf control.
X
Exit the service menu.
“DCU500 GF” appears on the display.
X
Set the internal programme switch on the passive leaf drive to “II AUT”.
X
Connect the service terminal ST220 to the passive leaf control.
à
In the menu “Door parameters”, submenu “Number of leaves”: “2-leaf passive” for passive leaf control.
X
Exit the service menu.
“DCU500 SF” appears on the display.