TSA 160 NT
12
Safety sensor open and close
5.2 Safety sensor GC 342
à
Safety sensor GC 342
à
Follow installation instructions GC 342
à
Accessories (optional):
à
Remote control, mat. no. 100061
à
For further accessories see installation instructions GC 342
Sensor position
X
Install safety sensors on the door leaf as specified in the GC 342 installation instructions.
X
Setting the testing parameter.
à
DPS: Set
Te
to
0 2
(testing with GND).
à
ST220: Set “Output signals”, “Testing SI” to “Testing with GND”.
à
S1, S2: Set parameter 11 to 02 “Testing with GND”.
5.2.1 Monitoring closing and opening
3
1
2
-UB
+UB
COM
+
SIO
60 mA
Test
SIS
BN
GN
YE
WH
PK
GY
BU
RD
SIO
13
1
GND
2
24V
10 TST
SIO
SIS
11
1
GND
2
24V
10 TST
SIS
1
GC 342 hinge side
2
GC 342 opposite hinge side
3
Door transmission cable
Settings GC 342
à
See installation instructions GC 342.
à
GEZE recommends using the optional remote control to change the sensor parameters.
Settings DCU5
X
Setting the contact type parameter:
à
DPS:
Set
s1
and
s3
to
0 2
(normally closed contact) (factory setting).
à
ST220: Set the “Input signals”, “SI1 – terminal SIS”, “SI1 contact type” to “normally closed contact”
and “SI3 – terminal SIO”, “SI3 contact type” to “normally closed contact” (factory setting).
à
S1, S2: Set parameter 7 and 9 to 02 “normally closed contact”.
X
Setting the function parameter:
à
DPS: Set
f1
to the desired function and
f3
to
0 5
(SIO stop) or
0 6
(SIO stop SF GF).
à
ST220: Set the “Input signals”, “SI1 – terminal SIS”, “SI1 function” to the desired function and “SI3 – terminal
SIO”, “SI3 function” to “SIO stop” or “SIO stop SF GF”.
à
S1, S2: Set parameter 8 to the desired function.
Set parameter 10 to 05 “SIO Stop” or 06 (SIO stop SF GF).