TSA 160 NT
15
Safety sensor open and close
5.3.2 Monitoring opening
X
Setting the contact type parameter:
à
DPS: Set
s3
to
0 2
(“normally closed contact”)
(factory setting).
à
ST220: Set the “Input signals”, “SI3 – terminal
SIO” and “SI3 contact type” to “normally
closed contact” (factory setting).
à
S1, S2: Set parameter 9 to 02 “normally closed
contact”.
X
Setting the function parameter:
à
DPS: Set
f3
to
0 5
(SIO stop) or
0 6
SIO stop SF GF“).
à
ST220: Set the “Input signals”, “SI3 – terminal
SIO” and “SI3 function” to “SIO stop”
or “SIO stop SF GF”.
à
S1, S2: Set parameter 10 to 05 “SIO Stop”
or 06 “SIO stop SF GF”.
à
GC 334 module configuration: DIP1 = ON
1 GND
13 SIO
10 TST
2 24V
SIO
WH
YE
BN
-
+
GN
BU
-
+
RD
60mA
2
3
1
PK
VT
1
GC 334 module
2
Door transmission cable
3
GC 334 hinge side
5.3.3 Monitoring closing
X
Setting the contact type parameter:
à
DPS: Set
s1
to
0 2
(“normally closed contact”)
(factory setting).
à
ST220: Set the “Input signals”, “SI1 – terminal
SIS” and “SI1 contact type” to “normally
closed contact” (factory setting).
à
S1, S2: Set parameter 7 to 02 “normally closed
contact”.
X
Setting the function parameter:
à
DPS: Set
f1
to the desired function.
à
ST220: Set the “Input signals”, “SI1 – terminal
SIS” and “SI1 function” to the desired
function.
à
S1, S2: Set parameter 8 to the desired function.
à
GC 334 module configuration: DIP1 = OFF
1 GND
11 SIS
10 TST
2 24V
SIS
WH
YE
BN
-
+
GN
BU
-
+
RD
60mA
PK
VT
2
3
1
1
GC 334 module
2
Door transmission cable
3
GC 334 opposite hinge side