4-2
MIMIC DISPLAY UNDER NORMAL OPERATION
(d) Push inverter ON switch – To turn on the inverter, the inverter ON switch
and the control switch must be pressed simultaneously. The
inverter will start working and inverter output will be established
in 4 seconds. The load will automatically be transferred to the
inverter 3 seconds later. Now the UPS is in normal operation.
~
~
~
/
~ ~
~
/
~
(e) Check if the mimic LED is correct, as shown in the figure, above. All
warning LEDs on the right side are off, two LEDs: ‘INVERTER
ON’ and ‘INVERTER SS’ on the left side should be lit. If the load
is over 70%, the ‘70% LOAD’ LED will also be lit.
4.2. Shutdown Procedure
If you want to shutdown the UPS completely (no power at output or inside),
please follow the steps below. This procedure is for generally standard systems, 3
phases 4 wire “WYE” Input. For special inputs, please refer to the brief
instruction label in front of the PCB holder.
(a) Switch off the inverter – The inverter can be switched off by pressing the
inverter OFF switch and the control switch simultaneously. The
load will be automatically transferred to reserve without
interruption.
Summary of Contents for T3UPS-33-700K
Page 18: ...1 7 Dimension Drawings 10KVA 60KVA OUTLINE DRAWING 1 13 ...
Page 19: ...10KVA 60KVA INTERIOR DRAWING 1 14 ...
Page 20: ...75KVA 160KVA OUTLINE DRAWING 1 15 ...
Page 21: ...75KVA 160KVA INTERIOR DRAWING 1 16 ...
Page 22: ...175KVA 320KVA OUTLINE DRAWING 1 17 ...
Page 23: ...175KVA 320KVA INTERIOR DRAWING 1 18 ...
Page 24: ...INTER PCB DIAGRAM 1 19 ...
Page 31: ...1 ...
Page 35: ...3 3 ...
Page 70: ...ONE TO TWO SERIAL REDUNDANCY 8 3 ...
Page 77: ...Appendices Additional Data on Options UPSCOMTM UPSCALLTM DCMANTM ...
Page 80: ...3 ...
Page 81: ......