CABLE SIZE FOR INPUT
KVA INPUT In(A)
R/S/T(mm
2
) N(mm
2
)
20 277/480V
3
Φ
30 8 14
30 277/480V
3
Φ
45 8 14
40 277/480V
3
Φ
60 14 22
50 277/480V
3
Φ
75 22 38
60 277/480V
3
Φ
90 22 38
80 277/480V
3
Φ
120 38 60
100 277/480V
3
Φ
150 60 80
120 277/480V
3
Φ
180 80 100
160 277/480V
3
Φ
240 100 125
240 277/480V
3
Φ
346 60*2 80*2
320 277/480V
3
Φ
461 100*2 125*2
3-7