(e) It is necessary to guarantee the temperature and humidity values of the site into
which the UPS will be installed. These should be within the range allowed by the
specification. The UPS is capable of continuous normal operation within a
temperature range of 0
℃
(32
℉
) to 40
℃
(104
℉
). For optimal performance and
reliability, and to prolong UPS’s lifetime, it is recommended to keep the
environment temperature below 25
℃
, and humidity below 80%.
(f) If the UPS is installed outdoors, avoid direct exposure of the UPS to the sunlight,
wind, and rain. Avoid any exposure to sand or dust.
(g) The floor loading capacity should be high enough to endure the weight of the
UPS. The UPS is mounted on four right-angled steel angles. Insert corresponding
bolts and nut2 (dia.1/2”) into the floor for securing the UPS on the floor when it is
located in an area where earthquakes is possible, or where motion may occur, e.g.
vehicle mounted. Layout dimensions, in millimeters, are shown below.
3-2
Summary of Contents for T3UPS-33-700K
Page 18: ...1 7 Dimension Drawings 10KVA 60KVA OUTLINE DRAWING 1 13 ...
Page 19: ...10KVA 60KVA INTERIOR DRAWING 1 14 ...
Page 20: ...75KVA 160KVA OUTLINE DRAWING 1 15 ...
Page 21: ...75KVA 160KVA INTERIOR DRAWING 1 16 ...
Page 22: ...175KVA 320KVA OUTLINE DRAWING 1 17 ...
Page 23: ...175KVA 320KVA INTERIOR DRAWING 1 18 ...
Page 24: ...INTER PCB DIAGRAM 1 19 ...
Page 31: ...1 ...
Page 35: ...3 3 ...
Page 70: ...ONE TO TWO SERIAL REDUNDANCY 8 3 ...
Page 77: ...Appendices Additional Data on Options UPSCOMTM UPSCALLTM DCMANTM ...
Page 80: ...3 ...
Page 81: ......