Uninterruptible Power Supply (UPS) 

BW40T/BW55T/BW100T/BW120T 

Instruction Manual 

 

 

 

▪ 

This manual describes the significant points to be noted to maintain the safety while using the 

UPS. Therefore, ensure reading it carefully before installation and start using the UPS. 

▪ 

Store this manual near the UPS so it can be referenced whenever required. 

▪ 

This instruction manual may not be reproduced in whole or in part without the express written 

permission. 

▪ 

The contents of this instruction manual may change in the future, without notice. 

▪ 

Warranty is contained in the box. 

 

Summary of Contents for BW100T

Page 1: ...PS Therefore ensure reading it carefully before installation and start using the UPS Store this manual near the UPS so it can be referenced whenever required This instruction manual may not be reprodu...

Page 2: ...any of the above For devices involved in human safety and significantly affect the maintenance of public function the special considerations are required in the operation maintenance and management in...

Page 3: ...ore start using the UPS Contact the purchased store if you lost the manual Windows are registered trademarks of United States Microsoft Corporation in the United States and other countries Other compa...

Page 4: ...Procedure from installation to operation BW40T BW55T BW100T BW120T 4 Procedure from installation to operation Shows the procedure from installation to operation...

Page 5: ...charge 24 2 5 Initial Value Measurement for Backup Time 24 2 6 Battery recharge 24 3 Operation of the Uninterruptible Power Supply UPS 25 3 1 Basic operations including running and stopping the unit...

Page 6: ...attery measure the backup time 39 7 2 Replacing the battery 39 7 2 1 How to replace a battery 41 7 3 Cleaning 49 8 Using the UPS monitoring software 50 8 1 The outline on the UPS monitoring software 5...

Page 7: ...ications Danger product applications Never use this device for the following purposes which require extremely high reliability and safety The UPS is designed and manufactured for FA including PC and O...

Page 8: ...valves Overcurrent may damage the Uninterruptible Power Supply Connect to the power outlet commercial power supply with the following current capacity BW40T 5 0A or higher BW55T 6 0A or higher BW100T...

Page 9: ...t clip or bundle the cable while using Electric shock or fire can occur due to the cable damage or heat generation Stop using the UPS if the cable has damage and immediately ask for the repair For inf...

Page 10: ...ately switch off the Power button of the UPS and unplug the AC input plug from the power outlet commercial power supply It may cause a fire if continue using In a case of the UPS gets into above menti...

Page 11: ...ut of any short circuit between the battery connectors It may result in electric shock Cautions for battery replace The battery pack should be replaced on a stable flat place Hold the battery pack fir...

Page 12: ...replace Do not short the battery with metal objects That may cause electric shock heat generation or burn injury Electric energy may remain even in a used battery pack Do not throw the battery in the...

Page 13: ...hen after every six months and the storage temperature is 40 degrees Celsius or below then after every two months Turn off Power button of the UPS during storage Prevent the short circuit between the...

Page 14: ...r discharge state or the state where the degraded battery is connected Do not run the withstand voltage test The power supply input line contains the surge absorbing elements which are subject to dest...

Page 15: ...discharging and the power output from the UPS stops Shut down the PC by the appropriate procedure i e save the data while the UPS continues supplying power About Restart If the battery discharges dur...

Page 16: ...P 2P conversion plug One Instructions for Labels Indicating Operating Condition One English Labels for Operation Panel One Battery Replaced Date Label One Connection Cable USB One Rubber Foot Cover fo...

Page 17: ...0T BW120T 17 1 1 3 Name of Each Part The followings list the names of the UPS parts Refer to 2Installation and connection P 20 3Operation of the Uninterruptible Power Supply UPS P 25 and other section...

Page 18: ...1 Preparation 1 3 Name of Each Part BW40T BW55T BW100T BW120T 18 Back BW40T BW55T...

Page 19: ...t panel operation BW100T BW120T The operation display section can be rotated by 90 degrees by the placement whether it is vertical or horizontal Pull out the operation display section rotate it and pr...

Page 20: ...d in the figure below Compliance Product serial number is required whenever contacting us Check the product serial number on the top of the main body or the serial label on the accessory Correct Direc...

Page 21: ...When the UPS s output outlet is insufficient purchase necessary equipment such as a table tap and install it on the output outlet The input plug shape of the connected device is 2P can also be connect...

Page 22: ...then starts the self diagnostic test During the self diagnosis FU is displayed in Detected Value The status display icon is displayed as shown below When the self diagnosis test ends normally it switc...

Page 23: ...ion state The display is different from the above mentioned It is abnormal Turn off Power button once When the display is according to 3 3 How to Understand Beep Sound and Display P 27 treat it accord...

Page 24: ...rforming 2 5 Initial Value Measurement for Backup Time 2 5 Initial Value Measurement for Backup Time Measure the initial value of the UPS s backup time in your environment so it can be a standard when...

Page 25: ...ion 1 Press Power button for three or more seconds During the self diagnosis FU is displayed in Detected Value The status display icon is displayed as shown below When the self diagnosis test ends nor...

Page 26: ...recovers from the power failure or abnormal power The battery starts automatic charging Once the battery runs down completely the UPS s power output stops Then the UPS automatically restarts and star...

Page 27: ...hen the frequency is low The right digit only blinks When both voltage and frequency are low Both blink 10 Continu ation 0 5 second Interval ON ON Or Dischar ging Too many devices are connected The ca...

Page 28: ...only the Power button on the UPS again If the displayed detail does not change ask for the repair as a problem is suspected with the UPS 20 Continu ation 1 second Interval ON OFF Abnormal battery temp...

Page 29: ...to set 3 By selecting the setting option and pressing the Select switch for 2 to 3 seconds the setting options and set values turn from a lighted state to blinking state if it does not blink repeat th...

Page 30: ...Enabled Battery life counter 0 Disabled 1 Enabled factory setting Power button shutdown 0 UPS shutdown factory setting 1 UPS PC shutdown Restart level 0 9 0 90 0 factory setting Maximum Backup Time 0...

Page 31: ...us indicator battery replacement lamp blinks and the beeper sounds SEE ALSO Follow the directions for the solutions described in 3 2Beep sound How to see the display Page 27 Manual testing 1 By pressi...

Page 32: ...of power failure Set the Maximum backup time setting Items available 1 Complete beep stop 2 Voltage sensitivity mode setting 3 Cold start setting 4 Maximum backup time setting 5 Automatic self diagno...

Page 33: ...vices refer to the graph of the backup time to obtain an estimation of the initial value of the backup time This is also applied to checking the battery 1 Unify the total capacity power consumption of...

Page 34: ...nd external environmental conditions temperature etc The maximum value of the estimated backup time display is 99 9 minutes on LCD Load Type 20 40 50 60 80 100 120 150 180 200 210 240 250 270 300 330...

Page 35: ...circuit consists of an open collector circuit using a photo coupler a kind of electronic switch Pin assignment and signal name of contact port Signals Descriptions Input of backup stop signal BS The i...

Page 36: ...ignal 5 I Input of backup stop signal BS 6 O Trouble Signal output TR 7 O Battery Replacement Signal output WB 8 Factory default setting By setting utility it is possible to change the combination of...

Page 37: ...120T 37 6 Signal terminal specifications Signal output BU BL TR WB Type of signals Isolated output through a photo coupler Rated Voltage 35V or less Maximum current 50mA Input of backup stop signal BS...

Page 38: ...r eyes or skin wash it out with lots of clean water and consult your doctor Do not throw the unit into fire The lead battery in the unit may explode or leak dilute sulfuric acid Do not insert metal ob...

Page 39: ...ince purchase 30 degrees Celsius For the first 1 5 years after purchase When 1 5 or more years have passed since purchase 7 2 Replacing the battery The battery can be replaced either while the unit is...

Page 40: ...rns If the fluid contacts your eyes or skin wash it out with lots of clean water and consult your doctor The battery should not be disassembled or modified Doing so could cause dilute sulfuric acid le...

Page 41: ...0T 41 7 7 2 1 How to replace a battery BW40T BW55T Work carefully not to slide and fall the unit 1 Lay it slowly so that the left side of the unit is upward 2 both hands put on the battery cover and s...

Page 42: ...r with your left hand pull it out from the battery connector When it is difficult to pull it out because of tight connection pull it out while rocking the connector part back and forth Then grabbing t...

Page 43: ...sert the connector of the battery and battery cable red to the plus terminal with your left hand Then insert the connector of the battery cable black to the negative terminal Replacement battery pack...

Page 44: ...links By pressing Buzzer stop Enter button self diagnostic test start and display FU As the test complete normally C00 stops blinking 3 Press Scroll button again C01 is displayed Press Scroll button f...

Page 45: ...Work carefully not to slide and fall the unit 1 Lay it slowly so that the left side of the unit is upward 2 Pull the front cover towards you to remove it by hooking a finger Don t twist the cable and...

Page 46: ...5T BW100T BW120T 46 3 Slide it by holding the protruding portion of the plate cover to the right 1 and pull it towards you 2 to remove it If lay the front cover aside detach the cable from the catch 4...

Page 47: ...he connector on the rear of the battery pack is connected to the unit Battery pack for replacement For BW100T BW120T Model BWB120T You may hear a pop sound when you connect the battery but this sound...

Page 48: ...continuously S11 S21 C00 By choosing C00 and pressing Scroll button for a long time C00 blinks By pressing Buzzer stop Enter button self diagnostic test start and display FU As the test complete norm...

Page 49: ...t use chemicals such as thinner and benzene They cause deformation or discoloration 2 Removing dust from the AC input plug power supply output receptacles of the UPS Stop all the connected devices and...

Page 50: ...ollowing table for the response situation for OS Notes When manually starting during the scheduled operation using the UPS monitoring software To manually start up this unit after it has been stopped...

Page 51: ...Windows Server2003 Windows Server2003 x64 Editions Windows XP Windows XP Professional x64 Edition Serial USB 1 1 PowerAct Pro Simple Shutdown Software Linux Cent OS Ver 7 x Ver 6 x Ver 5 x Red Hat Lin...

Page 52: ...igh function supporting network Simple Shutdown Software PowerAct Pro PowerAttendantLite Functions of softs Auto shutdown UPS monitoring operating status UPS monitoring data Pop up notification Shutdo...

Page 53: ...that can be set vary according to the UPS External command execution By executing commands at shutdown items such as application programs can be launched Event log save Information of events that occ...

Page 54: ...kup time on Page 33 For details see the manual for the above software 8 2 2 Simple Shutdown Software Simple Shutdown Software allows you to automatically shut down your PC when a power failure occurs...

Page 55: ...to stop the UPS at the same time that commercial power stops specify a period of no more than 3 months for the start of the next operation If you specify a period longer than 3 months the internal ti...

Page 56: ...rt of the PC which may damage files and the hard disk You can avoid this phenomenon by disabling POWER MANAGEMENT in the BIOS settings of the PC 1 Certain PC It is known that this phenomenon occurs fo...

Page 57: ...Battery Mode AC100V 6 Output frequency In Commercial Power Mode Input frequency through output Output frequency In Battery Mode 50 60Hz 0 1Hz Phase Single phase two wire grounded Output waveform In C...

Page 58: ...munication interface USB contact Noise regulation VCCI Class B Safety standard compliance UL1778 CE Noise 40 dB max 1 Make sure that both the VA value and the W value of the load capacity connected to...

Page 59: ...9 References 9 3 Circuit block diagram BW40T BW55T BW100T BW120T 59 9 BW100T BW120T 9 3 Circuit block diagram...

Page 60: ...9 4 Related products BW40T BW55T BW100T BW120T 60 9 4 Related products For BW40T BW55T For BW100T BW120T Replacement battery pack BWB55T BWB120T Bracket BWP55T BWP120T USB cable BUC30 Contact signal...

Page 61: ...NUD D 17063A No part or whole of this manual may be reproduced without permission The contents of this manual are subject to change without notice...