9 References
9-1 Specifications
BW40T/BW55T/BW100T/BW120T
57
9
9 References
9-1 Specifications
Model
BW40T
BW55T
BW100T
BW120T
Method
Operation method
Full-time commercial power supply method
method
Natural air cooling
Connectable devices
PC, display, and peripherals
Input
Rated input voltage
AC100V
Startup voltage range and input
voltage range
Standard sensitivity setting 86±3 to 114±3 VAC
High voltage sensitivity setting 95±3 to 108±3 VAC
Input Frequency
50/60Hz±4Hz
Maximum current
5A
6A
11A
12A
Phase
Single-phase, two-wire (grounded)
Input plug
NEMA5-15P
Input protection
Reset-type over current protection
Input protection capacity
10A
15A
Output
Output capacity (shared
maximum) *1
400VA/250W 550VA/340W 1000VA/610W 1200VA/730W
Output voltage (In Commercial
Power Mode)
Input voltage through output
Output voltage (In Battery Mode)
AC100V±6%
Output frequency (In
Commercial Power Mode)
Input frequency through output
Output frequency (In Battery
Mode)
50/60Hz±0.1Hz
Phase
Single-phase, two-wire (grounded)
Output waveform
(In Commercial Power Mode/
Battery Mode)
Sine wave/sine wave
Waveform distortion rate
(In Battery Mode)
25% or less
Output receptacle
NEMA 5-15R x 4 receptacles
Switching time
10 msec. max
Battery
Backup time (*2)
5.4 min. or
more
3.6 min. or
more
4.3 min. or
more
3.6 min. or
more
Type
Compact sealed lead battery
Battery life expectancy
5 years (long operating life) *At ambient temperature of 25
Battery capacity (V/Ah/quantity)
12 VDC / 7.8Ah / 1
12 VDC / 7.8Ah / 2
Charging time
12 hours
Environ
ment
Operating environment
temperature/humidity
0 to 40 degrees Celsius / 25 to 85% RH (with no condensation)
Storage environment
temperature/ humidity
-15 to 40 degrees Celsius / 10 to 90% RH (Store with battery
fully charged and with no condensation)
Lightening surge protection function
Available
Dimensions (W x D x H) *3
90 x 291 x 165 mm
85 x 342 x 235 mm