2 Installation and connection
2-3 Check the Operation
BW40T/BW55T/BW100T/BW120T
23
2
3.
Check the status display of the UPS in this state.
Status display
Power output outlet
Output the power (in a state where
connected equipment is conducted)
The display shows the
way as mentioned
above ->
The operation is normal. Go to the procedure 4.
The display is
different from the
above mentioned ->
It is abnormal. The display shows either one of those
mentioned in “3-3 How to Understand Beep Sound and
Display” (P.27.)
Go to the procedure 4 after the treatment according to the
handling method.
4.
Pull out the AC input plug of the UPS from the power outlet (commercial power
supply.)
It goes in the backup operation state.
5.
Check the status display of the UPS in the backup operation state.
The display is different from
the above mentioned ->
It is abnormal. Turn off "Power" button once.
- When the display is according to "3-3 How to
Understand Beep Sound and Display” (P.27,) treat it
according to the handling method and return to the
procedure 1 again.
- If the UPS and connected equipment stop without
backing up at all, the battery might have required more
charging.
Connect the UPS's "AC input" plug to the power outlet
(commercial power supply) and charge the battery for
over 12 hours, and then return to the procedure 4 again.
- If the problem persists after attempting the above two
methods, contact OMRON Electronic Equipment
Customer Support Center.
6.
Connect "AC input" plug to the power outlet (commercial power supply) again.
The status display goes back to the original.
Status display
Description
Power ON
Normally operating
That’s all for the operation check.
The installation process has been completed.
The operation is normal. Go to the procedure 6.