Safety Precautions
BW40T/BW55T/BW100T/BW120T
10
For information about repair, contact Omron Electronics Repair Center.
Replace the battery as soon as the life ends, or discontinue the use of
the UPS.
+ Continue using it may cause a fire or electric shock due to the liquid leakage.
Ambient
temperature
Expected life * The table on the left shows the expected
life under the standard usage conditions,
not the guaranteed values.
25 degrees
Celsius
5 years
30 degrees
Celsius
3.5 years
40 degrees
Celsius
1.7 years
Wipe off the dust on the "AC input" plug and the power output outlet
occasionally.
+ It may cause a fire if the dust residues for a long time.
+ Stop all the connected equipment and the UPS and unplug the "AC input" plug
from the power outlet (commercial power supply) before wiping off the dust.
Do not use it in a sealed place, and do not cover it.
+ It may cause an abnormal heat or fire.
+ Depending on your environment, hydrogen gas may be generated from the battery,
which can cause burst or explosion. Keep ventilating around the UPS.
In a case of unusual noise or odor, smoke, or liquid leaks from inside,
immediately switch off the "Power" button of the UPS and unplug the
"AC input" plug from the power outlet (commercial power supply.)
+ It may cause a fire if continue using.
+ In a case of the UPS gets into above-mentioned, immediately stop using it, unplug
the AC input cable, and then ask for inspection/repair either for the dealer or
Omron Electronics Repair Center.
+ Use the UPS in a state where "AC input" plug can be unplugged from the power
outlet (commercial power supply) immediately when an abnormality occurs.
Do not touch the liquid leaked from inside.
+ Doing so may cause blindness or burns.
+ In case the liquid is in touch with an eye or skin, clean it off with a large amount of
clean water and see a doctor.
Do not place things on the top, nor drop heavy objects on it.
+ It may cause a fire due to the distortion or breakage of the case, or internal circuit
failure.
The UPS is equipped with a bypass output circuit that allows the unit to continue supplying power
to the connected devices even when the internal control circuit function stops due to a failure or
malfunction.
Stop the supply of "commercial power supply" or unplug the "AC input" plug if you want to stop
output.
+
Output continues even if all the displays on the display section is off.
+
The output ON / OFF operation with "Power" button on the front will disable.