CHAPTER 7: MAINTENANCE
M3 BREAKER MAINTENANCE
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
7–7
RLY1(2) COIL DELAY
Range: 1 to 10 sec in steps of 1 sec
Default: 5 s
This setting defines the RLY1(2) Coil Monitor Delay, before targets appear on the display,
“ALARM” and “MAINTENANCE” LEDs light up on the front panel, and selected output
relays operate.
BYPASS BKR STATUS
Range: Disabled, Enabled
Default: Disabled
Set the “BYPASS BKR STATE” to Enabled when a by-pass resistor is connected across the
breaker auxiliary contact for continuous RLY1(2) circuit integrity monitoring. The circuits
will be monitored regardless of breaker position. When “BYPASS BKR STATE” is set to
Disabled, monitoring of the RLY1(2) coil will be blocked when the breaker is open.
OUTPUT RELAY 3 to 6
Range: Do not operate, Operate
Default: Do not operate
Any, or all, of output relays 3 to 6 can be selected to operate upon detection of RLY1(2)
Coil, or a RLY1(2) coil circuitry problem. The selection of the relay outputs operation is
available no matter whether the Alarm, or Latched Alarm, function is selected.