CHAPTER 6: SETPOINTS
S2 SYSTEM SETUP
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
6–47
S2 System Setup
Figure 11: System Setup menu
Current sensing
PATH
:
SETPOINTS > S2 SYSTEM SETUP > CURRENT SENSING
W1 PH CT PRIMARY
Range: 1 A to 6000 A in steps of 1 A
Default: 5 A
Enter the rated phase CT primary current of the three-phase current transformers
associated with Winding 1.
S2 CURRENT SENSING
W1 PH CT PRIMARY
W1 GND CT PRIMARY
W2 PH CT PRIMARY
W2 GND CT PRIMARY
▼
S2 SYSTEM SETUP
CURRENT SENSING
POWER SYSTEM
TRANSFORMER
WNDG 1 BREAKER
WNDG 2 BREAKER
▼
897765A1.cdr
S2 WNDG 1 BREAKER
52b CONTACT
52a CONTACT
BKR CONNECTED
▼
S2 POWER SYSTEM
SYSTEM ROTATION
NOMINAL FREQUENCY
▼
S2 TRANSFORMER
XFMR RATED LOAD
XFMR TYPE
PHASE COMPENSATION
W1 NOM VOLTAGE
W1 GROUNDING
W2 NOM VOLTAGE
W2 GROUNDING
▼
S2 WNDG 2 BREAKER
52b CONTACT
52a CONTACT
BKR CONNECTED
▼
W1 SENS GND PRIM
5 A
W2 SENS GND PRIM
5 A