6–48
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
S2 SYSTEM SETUP
CHAPTER 6: SETPOINTS
W1 PH CT SECONDARY
Range: 1 A to 5 A in steps of 1 A
Default: 1 A
Configurable 1 A or 5 A secondary (must be specified with order code P0G0). Enter the
rated phase CT secondary current of the three-phase current transformers associated
with Winding 1.
W1 GND CT PRIMARY
Range: 1 A to 6000 A in steps of 1 A
Default: 5 A
Enter the rated ground CT primary current of the ground current transformers
associated with Winding 1.
W1 GND CT SECONDARY
Range: 1 A to 5 A in steps of 1 A
Default: 1 A
Configurable 1 A or 5 A secondary (must be specified with order code P0G0). Enter the
rated ground CT secondary current of the ground current transformers associated with
Winding 1.
W2 PH CT PRIMARY
Range: 1 A to 6000 A in steps of 1 A
Default: 5 A
Enter the rated phase CT primary current of the three-phase current transformers
associated with Winding 2.
W2 PH CT SECONDARY
Range: 1 A to 5 A in steps of 1 A
Default: 1 A
Configurable 1 A or 5 A secondary (must be specified with order code P0G0). Enter the
rated phase CT secondary current of the three-phase current transformers associated
with Winding 2.
W2 GND CT PRIMARY
Range: 1 A to 6000 A in steps of 1 A
Default: 5 A
Enter the rated ground CT primary current of the ground current transformers
associated with Winding 2.
W2 GND CT SECONDARY
Range: 1 A to 5 A in steps of 1 A
Default: 1 A
Configurable 1 A or 5 A secondary (must be specified with order code P0G0). Enter the
rated ground CT secondary current of the ground current transformers associated with
Winding 2.
Power system
PATH
:
SETPOINTS > S2 SYSTEM SETUP > POWER SYSTEM
NOMINAL FREQUENCY
Range: 60 Hz, 50 Hz
Default: 60 Hz
Enter the nominal power system frequency. This value is used as a default to set the
optimal digital sampling rate.