CHAPTER 6: SETPOINTS
S1 RELAY SETUP
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
6–11
RS485 interface
The 345 is equipped with one serial RS485 communication port. The RS485 port has
settings for baud rate and parity. It is important that these parameters agree with the
settings used on the computer or other equipment that is connected to these ports. This
port may be connected to a computer running the EnerVista SR3 Setup software. This
software can download and upload setting files, view measured parameters, and upgrade
the device firmware. A maximum of 32 345-series devices can be daisy-chained and
connected to a DCS, PLC, or PC using the RS485 port.
Select the
Settings > Communications > Serial Ports
menu item in the EnerVista SR3
Setup program, or the
SETPOINTS > S1 RELAY SETUP > COMMUNICATIONS > RS485
path on
the display, to configure the serial port.
Figure 5: Serial port configuration settings
The following settings are available to configure the RS485 port.
BAUD RATE
Range: 9600, 19200, 38400, 57600, 115200
Default: 115200
This setting specifies the baud rate (bits per second) for the RS485 port.
PARITY
Range: None, Odd, Even
Default: None
This setting specifies the parity for the RS485 port.
REAR RS485 PROTOCOL
Range: Modbus, IEC60870-5-103, DNP 3.0
Default: Modbus
This setting specifies the protocol to be used for the rear RS485 port.
Ethernet
Select the
Setpoints > S1 Relay Setup > Communications > Ethernet
menu item in the
EnerVista SR3 Setup program, or the
SETPOINTS > S1 RELAY SETUP > COMMUNICATIONS >
ETHERNET
path on the display, to configure the Ethernet port.
The following settings are available to configure the Ethernet port.
IP Address
Range: Standard IP Address format
Default: 000.000.000.000
This setting specifies the IP Address for the Ethernet port.
Subnet IP Mask
Range: Standard IP Address format
Default: 255.255.255.000
This setting specifies the Subnet IP Mask setting for the Ethernet port.
Gateway IP Address
Range: Standard IP Address format
Default: 000.000.000.000
This setting specifies the Gateway IP Address for the Ethernet port.