6–132
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
S5 INPUTS/OUTPUTS
CHAPTER 6: SETPOINTS
BLOCK RLY 2 TRIP
Range: Disabled, Contact Input 1 to 10, Virtual Input 1 to 32, Remote Input 1 to 32, Logic
Elements 1 to 16
Default: Disabled
This setting defines a block to the Close Output relay. When the selected input is
asserted, the Close Output relay will be blocked. The block function can be useful for
breaker maintenance purposes.