CHAPTER 2: USING THE RTT ON SR SERIES RELAYS
THE SR750/760 FEEDER MANAGEMENT RELAY
RTT DESKTOP TEST SET– INSTRUCTION MANUAL
23
2.2.4
RTT to SR750/760 Wiring Diagram
1.
Ensure that Wet/Dry Input Type switch is set to
DRY
before applying power to the RTT
unit. The SR750 Relay accepts only
DRY
contact connections from the RTT.
2.
Ensure that current and voltage knobs are turned fully counter-clockwise before
applying power to the RTT unit.
Note
*750/760 doesn’t have RTD function.
**Trip and Alarm Common terminals (F2 and F3) must be hardwired together.
Table 2–2: SR750/760 with RTT Set to Dry
RTDs*
RTD3 +
RTD3 -
RTD3 C
RTD2 +
RTD2 -
RTD2 C
RTD1 +
RTD1 -
RTD1 C
SPARE
Contact
Outputs**
CLOSE COMMON
F3
-------------
RTT
TRIP COMMON
F2
-------------------------
OUTPUT C
CLOSE NO
E3
-------------------------
OUTPUT 2
TRIP NO
E2
-------------------------
OUTPUT
1
Contact
Inputs
+32 V DC
C11
-------------------------
INPUT C
Logic Input 7
C7
-------------------------
INPUT 8
Logic Input 6
C6
-------------------------
INPUT 7
Logic Input 5
C5
-------------------------
INPUT 6
Logic Input 4
C4
-------------------------
INPUT 5
Logic Input 3
C3
-------------------------
INPUT 4
Logic Input 2
C2
-------------------------
INPUT 3
Logic Input 1
C1
-------------------------
INPUT 2
Access
C10
-------------------------
INPUT
1
CTs
Ia (5A)
G7
-------------------------
I
+
Ia COM
H7
-------------------------
I
-
VTs
VA
H6
-------------------------
V
+
Vn
G5
-------------------------
V
-