RPV311
Chapter 4
– Configuration
RPV311-TM-EN-7
71
Figure 27: Adding and editing a voltage threshold
A
The <A
PPLY
ALL
> button allows user to apply the hold time or the hysteresis for all
thresholds.
B
The <R
EMOVE
> button allows user to delete the threshold.
8.2
Adding New Current Thresholds
To add a current threshold, fill in the following:
The S
OURCE
scroll box allows user to define a code of a current circuit used. No editing
allowed;
The Q
UANTITY
scroll box allows user to select the associated magnitude to be
monitored. For current circuits:
ABC
and
N
- magnitude or effective value;
ABC1
and
N1
- phasors;
𝑆
+
- positive sequence;
𝑆
−
- negative sequence;
IIMB
- imbalance;
IFRQ
- frequency;
ITHD
- total harmonic distortion;
dABC
and dN:
- magnitude or effective value variation;