The <R
ENAME
> button allows user to rename the digital channel.
The <R
EMOVE
> button allows user to delete the digital channel.
7
DC Channels
The signal of the transducer (±10 V or 0-20 mA) is converted in to the desired physical
measurement using a first order transfer function with the parameters of gain (
𝐴
)
and offset (
𝐵
) defined by the user:
𝑦 = 𝐴𝑥 + 𝐵
where
𝑦
is the converted value and
𝑥
is the value read by the DC channel in Volts or
Amps.
The RMS value of the DC channels (transducers) is calculated every cycle.
To add a new DC channel select the DC
C
HANNELS
section and fill in the following:
The I
DENTIFIER
text field allows user to enter a single code for the channel being
defined (maximum 15 characters). No editing allowed;
The I
NPUT
scroll box allows user to define the input to which each DC channel is
connected. No editing allowed;
The F
REQUENCY
REFERENCE
scroll box allows user to select a reference voltage circuit;
The G
AIN
and the O
FFSET
text field allows user to define the transfer connected
transducer function;
The U
NIT
text field allows user to define the connected transducer unit (maximum 6
characters, letters only).
Once the DC channel is created, it shows in the configuration interface menu. When
selecting the DC channel, a screen shows the characteristics of the DC channel
selected, as shown in Figure 26. It is possible to edit the frequency reference, gain,
offset and unit.
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...