8.4
Adding New Digital Thresholds
To add a digital threshold, fill in the following:
The S
OURCE
scroll box allows user to define a code of a digital channel used. No
editing allowed;
The C
ONDITION
scroll box allows user to select the threshold condition:
(blank) - High level;
(!)
- Low level;
(
∧
)
- Rising edge;
(
∨
)
- Falling edge.
Once the threshold is created, it shows in the configuration interface menu. When
selecting the threshold, a screen shows its operator and identifier.
The <R
EMOVE
> button allows user to delete the threshold.
8.5
Adding New DC Thresholds
To add a DC threshold, fill in the following:
The Source scroll box allows user to define a code of a DC channel used. No
editing allowed;
The Operator scroll box allows user to select greater than or less than for
analog magnitude;
The Value text field allows user to enter the magnitude value associated
with greater than or less than operator;
The Hold time text field allows user to enter the time in milliseconds, where
the threshold needs to be exceeded to be considered valid;
The Hysteresis text field allows user to enter a quantity in
%
, whose value
needs to be smaller in relation to the threshold to determine the event end
and reset the threshold detector.
Once the threshold is created, it appears in configuration interface menu. When
selecting the threshold, a screen shows the characteristics of the threshold selected,
as shown in
. It is possible to edit the value, hold time and hysteresis.
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...