RPV311
Chapter 15
– Installation
RPV311-TM-EN-7
222
The RA331 and RA332 modules each occupy one physical link of the processing
module. The RA333 occupies two physical links of the processing module, one for
data transmission of analog channels (DFR) and the other for data transmission of
TW channels (TW).
On the RA331, RA332 and RA333 (TW and DFR) modules, each link has an indicator
showing the state of the connection with the processing module, as shown in
. These indicators, L
INK
and A
CT
, on the front panel and back panel, respectively,
light up when the link is active (i.e. it is receiving requests of the processing module).
Figure 111: RA331, RA332 and RA333 fiber optic connectors
The connectors are identified as RX for receiving data and TX for transmitting data.
The corresponding fibers must be linked to the acquisition module so that the TX of
RPV311 is connected to the RX of the RA331, RA332, or RA333 and RX of RPV311 is
connected to the TX of the RA331, RA332, or RA333, according to
Figure 112: Connection between RPV311 and the RA331, RA332 or RA333
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...