Chapter 4
– Configuration
RPV311
76
RPV311-TM-EN-7
Figure 30: Adding and editing a DC threshold
A
The <A
PPLY
ALL
> button allows user to apply the hold time or the hysteresis for all
threshold.
B
The <R
EMOVE
> button allows user to delete the threshold.
9
Cross-Trigger
The cross-trigger is performed through an Ethernet broadcast UDP message sent
whenever the device triggers, then all the RPV311 within the network with the cross-
trigger enabled will receive the message and trigger as well.
10
Fault Recorder
The RPV311 allows user to register triggered and continuous fault recorder.
10.1
Trigger’d Recording
In this section, shown in
, it is possible to configure the equipment's fault
triggered recorder.