RPV311
Chapter 4
– Configuration
RPV311-TM-EN-7
79
The RPV311 allows user to configure triggered and continuous disturbance
recording.
11.1
Trigger'd Recording
In this section, shown in
, it is possible to configure the equipment
disturbance triggered recorder.
Figure 33: Disturbance recorder
– trigger’d recording configuration
A
The E
NABLED
check box allows user to enable the disturbance triggered recorder
feature.
B
The P
RE
TIME
text field allows user to enter the recording time before the event in
seconds. The P
OST
TIME
text field allows user to enter the recording time after the
event in seconds. The T
IME OUT
text field allows user to enter the maximum times in
seconds, where the event will be recorded. The D
ISABLED FOR
–
MINUTES IF MORE THAN
–
TRIGGERS IN THE LAST
–
SECONDS
allows user to disable recorder if the event repeats within
a programmed time period.