Chapter 8
– PMU
RPV311
156
RPV311-TM-EN-7
The WMU transmits Ethernet messages that are analogue signals calculated and
sent within a PMU frame with a transmission rate equal to 4 times the system
nominal frequency.
The analog signal sent is a representation of a three-phase signal that is used to
evaluate wide-area subcyclic oscillations. The WMU uses the analogue field (No 10) of
the frame below to send its data.
The WMU uses the commanded logic through the port number
4723.
The table below exemplifies a frame of PMU described as per IEEE C37.118.2-2011.
N
o
Field
Size
(bytes)
Comment
1
SYNC
2
Sync byte followed by frame type and version number
2
FRAMESIZ
E
2
Number of bytes in frame
3
IDCODE
2
Stream source ID number, 16-bit integer
4
SOC
4
SOC timestamp, for all measurements in frame.
5
FRACSEC
4
Fraction of Second and Time Quality, for all measurements in frame.
6
STAT
2
Bit mapped flags.
7
PHASORS
4 x
PHNMR
or
8 x
PHNMR
Phasor estimates. May be single phase or 3-phase positive,
negative, or zero sequence. 4 or 8 bytes each depending on
the fixed 16-bit or floating point format used, as indicated
by the FORMAT field in configuration the frame. The
number of values is determined by the PHNMR field in
configuration 1, 2, and 3 frames.
8
FREQ
2 / 4
Frequency (fixed or floating point).
9
DFREQ
2 / 4
Rate of change of frequency (fixed or floating point).
10
ANALOGU
E
2 x
ANNMR
or
4 x
ANNMR
Analog data, 2 or 4 bytes per value depending on fixed or
floating point format used, as indicated by the FORMAT
field in configuration 1,2, and 3 frames. The number of
values is determined by the ANNMR field in configuration 1,
2, and 3 frames.
11
DIGITAL
2 x
DGNM
R
Digital data, usually representing 16 digital status points
(channels). The number of values is determined by the
DGNMR field in configuration 1, 2, and 3 frames
Repeat 6
–
11
4 x
ANNMR
Fields 6 - 11 are repeated for as many PMUs as in NUM_PMU field in
configuration frame.
12
+
CHK
2
CRC-CCITT
.
Summary of Contents for RPV311
Page 2: ......
Page 44: ......
Page 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Page 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Page 142: ......
Page 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Page 152: ......
Page 160: ......
Page 162: ......
Page 164: ......
Page 204: ......
Page 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Page 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...