Commissioning
P74x/EN CM/Na7
MiCOM P741, P742, P743
(CM) 10-29
CM
I
bias
is fixed to a lowest value of ID>2/k2 and IDCZ>2/kCZ, the Az and Acz points will thus be
ID>2 and IDCZ>2. So I
bias
= I
1
+ I
2
= fixed value (Points A)
To test the slopes:
I
bias
is fixed to a value greater than ID>2/k2 and IDCZ>2/kCZ the Bz and Bcz points will thus
be I
bias
x k2 and I
bias
x kCZ. So I
bias
= I
1
+ I
2
= fixed value (Points B)
When we reach the point Xcz the Central Unit LED 8 and relay 8 will operate and when we
reach the point Xz the differential element will operate.
To calculate the slope k, k = (I
1
– I
2
) / (I
1
+ I
2
)
The differential current will increase twice the value
I.
Note 1:
I
D
>1 alarm timer will be set to 100s during the test.
Note 2:
Whenever possible, inject 2
×
I
D
>2. Alternatively, the minimum current
must be higher than 1.7
×
I
D
>2 at 60Hz and I.42
×
I
D
>2 at 50Hz in
order to ensure a 15ms tripping time
6.3.1.2
Slopes and thresholds
If a LED has been assigned in central or/and peripheral units to display the trip information,
these may be used to indicate correct operation. If not, monitor option will need to be used –
see the next paragraph.
On P741 go Central Unit GROUP1-->BUSBAR PROTECT and set I
D
>1 Alarm timer to 100s
On P742/3 go to COMMISSION TESTS column in the menu, scroll down and change cells
[Monitor Bit 1] to [BUSBAR_TRIPPING]. Doing so, cell [Test Port Status] will appropriately
set or reset the bits that now represent BUSBAR_TRIPPING (with the rightmost bit
representing Busbar Trip. From now on you should monitor the indication of [Test Port
Status]. Make a note of which elements need to be re-enabled or re-set after testing.
Test of I
D
>2:
I
D
>1 Alarm Timer should be set to 100s during testing.
Inject a I
2
current smaller than I
D
>2 and slowly increase I
2
until tripping.
Test of the operating time of the differential element:
Inject a I
2
current greater than twice I
D
>2 threshold and measure the operating time of the
differential element.
Test of I
D
>1:
I
D
>1 Alarm Timer should be set to 100ms.
Inject a I
2
current smaller than I
D
>1 and slowly increase I
2
until circuit fault appears (LED
Alarm of LED circuitry fault).
Test of I
D
>1 Alarm Timer:
I
D
>1 Alarm Timer should be set to 5s.
Inject a I2 current greater than twice the I
D
>1 threshold and check that the Circuitry Fault
Alarm is coming in 5s.
Note: Same tests can be applied for the Differential Sensitive Earth Fault Protection.
Note: the Sensitive Differential Earth Fault (SDEF) is 20ms delayed and controlled by a
settable threshold I
bias
ph> to unblock/block the sensitive element depending of the restrain
phase currents.
IMPORTANT NOTE: Check that if the SDEF is enabled, all the CTs are of the same
standard.
Summary of Contents for P741
Page 2: ......
Page 4: ......
Page 6: ...P74x EN IT Na7 Introduction MiCOM P741 P742 P743 ...
Page 8: ...P74x EN IT Na7 Introduction IT 1 2 MiCOM P741 P742 P743 IT ...
Page 18: ...P74x EN TD Na7 Technical Data MiCOM P741 P742 P743 ...
Page 30: ...P74x EN TD Na7 Technical Data TD 2 14 MiCOM P741 P742 P743 TD ...
Page 32: ...P74x EN GS Na7 Getting Started MiCOM P741 P742 P743 ...
Page 70: ...P74x EN ST Na7 Getting Started MiCOM P741 P742 P743 ...
Page 72: ...P74x EN ST Na7 Settings ST 4 2 MiCOM P741 P742 P743 ST ...
Page 116: ...P74x EN OP Na7 Operation MiCOM P741 P742 P743 ...
Page 120: ...P74x EN OP Na7 Operation OP 5 4 MiCOM P741 P742 P743 OP ...
Page 136: ...P74x EN OP Na7 Operation OP 5 20 MiCOM P741 P742 P743 OP FIGURE 8 CB FAIL LOGIC ...
Page 166: ...P74x EN AP Na7 Application Notes MiCOM P741 P742 P743 ...
Page 234: ...P74x EN PL Na7 Programmable Logic MiCOM P741 P742 P743 ...
Page 290: ...P74x EN PL Na7 Programmable Logic PL 7 56 MiCOM P741 P742 P743 PL ...
Page 291: ...Programmable Logic P74x EN PL Na7 MiCOM P741 P742 P743 PL 7 57 PL ...
Page 292: ...P74x EN PL Na7 Programmable Logic PL 7 58 MiCOM P741 P742 P743 PL ...
Page 294: ...P74x EN PL Na7 Programmable Logic PL 7 60 MiCOM P741 P742 P743 PL ...
Page 295: ...Programmable Logic P74x EN PL Na7 MiCOM P741 P742 P743 PL 7 61 PL ...
Page 296: ...P74x EN PL Na7 Programmable Logic PL 7 62 MiCOM P741 P742 P743 PL ...
Page 298: ...P74x EN PL Na7 Programmable Logic PL 7 64 MiCOM P741 P742 P743 PL ...
Page 299: ...Programmable Logic P74x EN PL Na7 MiCOM P741 P742 P743 PL 7 65 PL ...
Page 300: ...P74x EN PL Na7 Programmable Logic PL 7 66 MiCOM P741 P742 P743 PL ...
Page 302: ...P74x EN MR Na7 Measurements and Recording MiCOM P741 P742 P743 ...
Page 324: ...P74x EN FD Na7 Firmware Design MiCOM P741 P742 P743 ...
Page 344: ...P74x EN FD Na7 Firmware Design FD 9 20 MiCOM P741 P742 P743 FD FIGURE 10 P74x SYSTEM OVERVIEW ...
Page 351: ...Firmware Design P74x EN FD Na7 MiCOM P741 P742 P743 FD 9 27 FD ...
Page 353: ...P74x EN CM Na7 Commissioning MiCOM P741 P742 P743 ...
Page 429: ...P74x EN MT Na7 Maintenance MiCOM P741 P742 P743 ...
Page 431: ...P74x EN MT Ma7 Maintenance MT 11 2 MiCOM P741 P742 P743 MT ...
Page 451: ...P74x EN TS Na7 Troubleshooting MiCOM P741 P742 P743 ...
Page 453: ...P74x EN TS Na7 Troubleshooting TS 12 2 MiCOM P741 P742 P743 TS ...
Page 475: ...P74x EN SC Na7 SCADA Communications MiCOM P741 P742 P743 ...
Page 499: ...P74x EN SC Na7 SCADA Communications SC 13 24 MiCOM P741 P742 P743 SC ...
Page 501: ...P74x EN SG Na7 Symbols and Glossary MiCOM P741 P742 P743 ...
Page 511: ...P74x EN SG Na7 Symbols and Glossary SG 14 10 MiCOM P741 P742 P743 SG Logic Gates ...
Page 513: ...P74x EN IN Na7 Installation MiCOM P741 P742 P743 ...
Page 515: ...P74x EN IN Na7 Installation IN 15 2 MiCOM P741 P742 P743 IN ...
Page 528: ...Installation P74x EN IN Na7 MiCOM P741 P742 P743 IN 15 15 IN FIGURE 6 P742 40TE REAR VIEW ...
Page 533: ...P74x EN VH Na7 Firmware and Service Manual Version History MiCOM P741 P742 P743 ...
Page 542: ...APPENDIX A WIRING DIAGRAMS ...
Page 543: ...Appendix A Wiring Diagrams P74x P74x EN M Na7 ...
Page 559: ......