P74x/EN OP/Na7
Operation
(OP) 5-
10
MiCOM P741, P742, P743
OP
Table below shows operation depending on the thresholds' status.
I
D
>1
k1.
I
bias
I
D
>2
Status
Operation
0
0
0
Normal
No operation
1
0
0
Normal
No operation
0
1
0
Normal
No operation
1
0
1
External fault or
circuitry fault
External fault with CT saturation or
block circuitry fault alarm after t
CF
1
1
0
Circuitry fault
Block and circuitry fault alarm after t
CF
1
1
1
Internal fault
Trip
TABLE 1: OPERATION CONDITIONS
1.2.5
Signal Quality
An additional check is carried out to confirm that the signals used to determine the previous
criteria are satisfactory.
This includes checking for CT saturation conditions (information from peripheral unit, refer to
Section 2.1), that no plant discrepancies exist (via check zone as discussed earlier), and that
a change (increase or loss) in current flow has been detected by at least two peripheral units
(
I detection). The latter condition is used, as internal or external faults will cause a change
in levels in at least two circuits whereas, a CT fail only affect a single circuit’s level (faulty
CT).
Note:
This condition is used only when there is no dead bus condition.
When a trip is issued for a bus zone by the central unit a signal is sent to all peripheral units
associated (or not) with the faulted bus zone. The peripheral units associated with the faulted
zone can carry out a further local confirmation via local Overcurrent protection,
I
>BB or
I
N
>BB, before allowing a trip to take place.
1.2.6
Tripping Criteria
Before a trip signal is issued 4 trip criterions at the top level, i.e. the Central Unit, and 1
(optional) at the local level, i.e. the Peripheral Units, must be met.
These criterions are:
Top level (Central Unit)
Instantaneous criteria:
•
Bias characteristic ( I
diff
> (I
D
>2)) and Differential current setting are
exceeded (I
diff
> k2 I
bias
) for the zone for 2 consecutive samples
•
Bias characteristic ( I
diff
> (I
D
CZ>2)) and Differential current setting are
exceeded (I
diff
> kCZ I
bias
) for the check zone for 2 consecutive samples
•
No CT saturation
•
Signal quality (CT supervision, , AD converter, etc…)
Delayed criteria:
•
Bias characteristic ( I
diff
> (I
D
>2)) and Differential current setting are
exceeded (I
diff
> k2 I
bias
) for the zone for at least 1 sample
•
Bias characteristic ( I
diff
> (I
D
CZ>2)) and Differential current setting are
exceeded (I
diff
> kCZ I
bias
) for the check zone for at least 1 sample
•
Bias characteristic ( I
diff
> (I
D
>2)) and Differential current setting are not
exceeded (I
diff
> k2 I
bias
) for the zone for at least 1 sample in the 4 following
samples
Summary of Contents for P741
Page 2: ......
Page 4: ......
Page 6: ...P74x EN IT Na7 Introduction MiCOM P741 P742 P743 ...
Page 8: ...P74x EN IT Na7 Introduction IT 1 2 MiCOM P741 P742 P743 IT ...
Page 18: ...P74x EN TD Na7 Technical Data MiCOM P741 P742 P743 ...
Page 30: ...P74x EN TD Na7 Technical Data TD 2 14 MiCOM P741 P742 P743 TD ...
Page 32: ...P74x EN GS Na7 Getting Started MiCOM P741 P742 P743 ...
Page 70: ...P74x EN ST Na7 Getting Started MiCOM P741 P742 P743 ...
Page 72: ...P74x EN ST Na7 Settings ST 4 2 MiCOM P741 P742 P743 ST ...
Page 116: ...P74x EN OP Na7 Operation MiCOM P741 P742 P743 ...
Page 120: ...P74x EN OP Na7 Operation OP 5 4 MiCOM P741 P742 P743 OP ...
Page 136: ...P74x EN OP Na7 Operation OP 5 20 MiCOM P741 P742 P743 OP FIGURE 8 CB FAIL LOGIC ...
Page 166: ...P74x EN AP Na7 Application Notes MiCOM P741 P742 P743 ...
Page 234: ...P74x EN PL Na7 Programmable Logic MiCOM P741 P742 P743 ...
Page 290: ...P74x EN PL Na7 Programmable Logic PL 7 56 MiCOM P741 P742 P743 PL ...
Page 291: ...Programmable Logic P74x EN PL Na7 MiCOM P741 P742 P743 PL 7 57 PL ...
Page 292: ...P74x EN PL Na7 Programmable Logic PL 7 58 MiCOM P741 P742 P743 PL ...
Page 294: ...P74x EN PL Na7 Programmable Logic PL 7 60 MiCOM P741 P742 P743 PL ...
Page 295: ...Programmable Logic P74x EN PL Na7 MiCOM P741 P742 P743 PL 7 61 PL ...
Page 296: ...P74x EN PL Na7 Programmable Logic PL 7 62 MiCOM P741 P742 P743 PL ...
Page 298: ...P74x EN PL Na7 Programmable Logic PL 7 64 MiCOM P741 P742 P743 PL ...
Page 299: ...Programmable Logic P74x EN PL Na7 MiCOM P741 P742 P743 PL 7 65 PL ...
Page 300: ...P74x EN PL Na7 Programmable Logic PL 7 66 MiCOM P741 P742 P743 PL ...
Page 302: ...P74x EN MR Na7 Measurements and Recording MiCOM P741 P742 P743 ...
Page 324: ...P74x EN FD Na7 Firmware Design MiCOM P741 P742 P743 ...
Page 344: ...P74x EN FD Na7 Firmware Design FD 9 20 MiCOM P741 P742 P743 FD FIGURE 10 P74x SYSTEM OVERVIEW ...
Page 351: ...Firmware Design P74x EN FD Na7 MiCOM P741 P742 P743 FD 9 27 FD ...
Page 353: ...P74x EN CM Na7 Commissioning MiCOM P741 P742 P743 ...
Page 429: ...P74x EN MT Na7 Maintenance MiCOM P741 P742 P743 ...
Page 431: ...P74x EN MT Ma7 Maintenance MT 11 2 MiCOM P741 P742 P743 MT ...
Page 451: ...P74x EN TS Na7 Troubleshooting MiCOM P741 P742 P743 ...
Page 453: ...P74x EN TS Na7 Troubleshooting TS 12 2 MiCOM P741 P742 P743 TS ...
Page 475: ...P74x EN SC Na7 SCADA Communications MiCOM P741 P742 P743 ...
Page 499: ...P74x EN SC Na7 SCADA Communications SC 13 24 MiCOM P741 P742 P743 SC ...
Page 501: ...P74x EN SG Na7 Symbols and Glossary MiCOM P741 P742 P743 ...
Page 511: ...P74x EN SG Na7 Symbols and Glossary SG 14 10 MiCOM P741 P742 P743 SG Logic Gates ...
Page 513: ...P74x EN IN Na7 Installation MiCOM P741 P742 P743 ...
Page 515: ...P74x EN IN Na7 Installation IN 15 2 MiCOM P741 P742 P743 IN ...
Page 528: ...Installation P74x EN IN Na7 MiCOM P741 P742 P743 IN 15 15 IN FIGURE 6 P742 40TE REAR VIEW ...
Page 533: ...P74x EN VH Na7 Firmware and Service Manual Version History MiCOM P741 P742 P743 ...
Page 542: ...APPENDIX A WIRING DIAGRAMS ...
Page 543: ...Appendix A Wiring Diagrams P74x P74x EN M Na7 ...
Page 559: ......