P74x/EN MR/Na7
Measurements and Recording
(MR) 8-
6
MiCOM P741, P742, P743
MR
VIEW RECORDS
Description
LCD Reference
Start Elements
Start I>1, Start I>2, Start I>2BB, Start I>BB, Start IN>1, Start
IN>2, Start IN>2BB, Start IN>BB
Trip Elements
Trip I>1, Trip I>2, Trip IN>1, Trip IN>2, Trip 87BB, Trip
CBFail tBF1, Trip CBFail tBF2, Trip CBFail tBF3, Trip CBFail
tBF4, Trip 50BF (CU), Manual Trip zone, Trip 87BB block,
Dead Zone Trip
Time Stamp
Time and date of fault recorder start
Fault Alarms
Yes, No
System Frequency
50.00 Hz, 60.00 Hz,
Relay Trip Time
Delay between reception of signal and end of trip on PU
IA
Feeder phase A current
IB
Feeder phase B current
IC
Feeder phase C current
IN
Feeder phase N current
Select Maint.
Setting range from 0 to 9. This selects the required
maintenance report from the possible 10 that may be stored.
A value of 0 corresponds to the latest report and so on.
Maint. Text
Up to 16 Character description of the occurrence (refer to
following sections).
Maint. Type/Main Data
These cells are numbers representative of the occurrence.
They form a specific error code which should be quoted in
any related correspondence to Report Data.
Reset Indication
Either Yes or No. This serves to reset the trip LED
indications provided that the relevant protection element has
reset, to reset all LED and relays latched in the PSL, and to
reset the latched alarms.
For extraction from a remote source via communications, refer to the SCADA
Communications section (P74x/EN CT), where the procedure is fully explained.
2.3
Types of event
An event may be a change of state of a control input or output relay, an alarm condition,
setting change etc. The following sections show the various items that constitute an event:
2.3.1
Change of state of opto-isolated inputs
If one or more of the opto (logic) inputs has changed state since the last time that the
protection algorithm ran, the new status is logged as an event. When this event is selected
to be viewed on the LCD, three applicable cells will become visible as shown below:
Time & date of event
“LOGIC INPUTS #”
“Event Value 0101010101010101”
Where # = 1 or 2 depending upon which group of 16 opto inputs is selected. In the case of
P74x relay, however, the value will always be “1” as it is impossible to have more than 16
opto inputs.
Summary of Contents for P741
Page 2: ......
Page 4: ......
Page 6: ...P74x EN IT Na7 Introduction MiCOM P741 P742 P743 ...
Page 8: ...P74x EN IT Na7 Introduction IT 1 2 MiCOM P741 P742 P743 IT ...
Page 18: ...P74x EN TD Na7 Technical Data MiCOM P741 P742 P743 ...
Page 30: ...P74x EN TD Na7 Technical Data TD 2 14 MiCOM P741 P742 P743 TD ...
Page 32: ...P74x EN GS Na7 Getting Started MiCOM P741 P742 P743 ...
Page 70: ...P74x EN ST Na7 Getting Started MiCOM P741 P742 P743 ...
Page 72: ...P74x EN ST Na7 Settings ST 4 2 MiCOM P741 P742 P743 ST ...
Page 116: ...P74x EN OP Na7 Operation MiCOM P741 P742 P743 ...
Page 120: ...P74x EN OP Na7 Operation OP 5 4 MiCOM P741 P742 P743 OP ...
Page 136: ...P74x EN OP Na7 Operation OP 5 20 MiCOM P741 P742 P743 OP FIGURE 8 CB FAIL LOGIC ...
Page 166: ...P74x EN AP Na7 Application Notes MiCOM P741 P742 P743 ...
Page 234: ...P74x EN PL Na7 Programmable Logic MiCOM P741 P742 P743 ...
Page 290: ...P74x EN PL Na7 Programmable Logic PL 7 56 MiCOM P741 P742 P743 PL ...
Page 291: ...Programmable Logic P74x EN PL Na7 MiCOM P741 P742 P743 PL 7 57 PL ...
Page 292: ...P74x EN PL Na7 Programmable Logic PL 7 58 MiCOM P741 P742 P743 PL ...
Page 294: ...P74x EN PL Na7 Programmable Logic PL 7 60 MiCOM P741 P742 P743 PL ...
Page 295: ...Programmable Logic P74x EN PL Na7 MiCOM P741 P742 P743 PL 7 61 PL ...
Page 296: ...P74x EN PL Na7 Programmable Logic PL 7 62 MiCOM P741 P742 P743 PL ...
Page 298: ...P74x EN PL Na7 Programmable Logic PL 7 64 MiCOM P741 P742 P743 PL ...
Page 299: ...Programmable Logic P74x EN PL Na7 MiCOM P741 P742 P743 PL 7 65 PL ...
Page 300: ...P74x EN PL Na7 Programmable Logic PL 7 66 MiCOM P741 P742 P743 PL ...
Page 302: ...P74x EN MR Na7 Measurements and Recording MiCOM P741 P742 P743 ...
Page 324: ...P74x EN FD Na7 Firmware Design MiCOM P741 P742 P743 ...
Page 344: ...P74x EN FD Na7 Firmware Design FD 9 20 MiCOM P741 P742 P743 FD FIGURE 10 P74x SYSTEM OVERVIEW ...
Page 351: ...Firmware Design P74x EN FD Na7 MiCOM P741 P742 P743 FD 9 27 FD ...
Page 353: ...P74x EN CM Na7 Commissioning MiCOM P741 P742 P743 ...
Page 429: ...P74x EN MT Na7 Maintenance MiCOM P741 P742 P743 ...
Page 431: ...P74x EN MT Ma7 Maintenance MT 11 2 MiCOM P741 P742 P743 MT ...
Page 451: ...P74x EN TS Na7 Troubleshooting MiCOM P741 P742 P743 ...
Page 453: ...P74x EN TS Na7 Troubleshooting TS 12 2 MiCOM P741 P742 P743 TS ...
Page 475: ...P74x EN SC Na7 SCADA Communications MiCOM P741 P742 P743 ...
Page 499: ...P74x EN SC Na7 SCADA Communications SC 13 24 MiCOM P741 P742 P743 SC ...
Page 501: ...P74x EN SG Na7 Symbols and Glossary MiCOM P741 P742 P743 ...
Page 511: ...P74x EN SG Na7 Symbols and Glossary SG 14 10 MiCOM P741 P742 P743 SG Logic Gates ...
Page 513: ...P74x EN IN Na7 Installation MiCOM P741 P742 P743 ...
Page 515: ...P74x EN IN Na7 Installation IN 15 2 MiCOM P741 P742 P743 IN ...
Page 528: ...Installation P74x EN IN Na7 MiCOM P741 P742 P743 IN 15 15 IN FIGURE 6 P742 40TE REAR VIEW ...
Page 533: ...P74x EN VH Na7 Firmware and Service Manual Version History MiCOM P741 P742 P743 ...
Page 542: ...APPENDIX A WIRING DIAGRAMS ...
Page 543: ...Appendix A Wiring Diagrams P74x P74x EN M Na7 ...
Page 559: ......